Inspections for the day of: Wednesday, March 13, 2019.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJames Ady
TitleELE-INSPECTOR
Phone #914-4683
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-00011 Final3/13/20193/13/20193/13/2019 1:44:43 PMPPASS
Phone #: ###-#### Inspection requested via web by Therrin Robertson final ok
ELE19-00237 Final3/12/20193/13/20193/13/2019 1:44:42 PMPFAIL
Please call Josh Goff 30 minutes before arriving ###-#### Phone #: ###-#### Inspection requested via web by Eric Schroeder 314.20. Boxes set back more than 1/4 shall have extension.(All receps and switches in kitchen backsplash.) Re-install devices in kitchen(Devices were removed to install tile) All items have been tested.
ELE19-00890 Final3/13/20193/13/20193/13/2019 12:33:26 PMPNH
Kaden Golay is the contact Phone #: ###-#### Inspection requested via web by William Salts No access/ Nobody home. re-call
ELE16-02464 ELE-Aging Inspection3/13/20193/13/20193/13/2019 12:13:55 PM PASS
Project complete ready for final
ELE16-02464 Final3/13/20193/13/20193/13/2019 12:13:25 PMPPASS
Ready for final. Final ok
ELE19-00787 Temporary Service3/13/20193/13/20193/13/2019 12:12:33 PMPPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE19-00822 Final3/12/20193/13/20193/13/2019 11:41:07 AMAPASS
Tim-homeowner Phone #: ###-#### Final ok
ELE19-00822 Electrical Rough-In3/13/20193/13/20193/13/2019 11:40:55 AMPPASS
Tim-homeowner Phone #: ###-#### Surface mounted conduit ok
ELE18-01857 Final3/13/20193/13/20193/13/2019 11:11:28 AMAFAIL
Partial final on 3rd floor Phone #: ###-#### Inspection requested via web by cris flores 440.6A Nameplate of equipment shall be used to determine branch circuit conductors and Disc size.(29.5amp min, 40amp max. 10awg min. 12awg ran.)
ELE18-04852 Final3/12/20193/13/20193/13/2019 10:00:16 AMAFAIL
please call Dena@###-#### she b home 9-3.
need inspection per prior request Phone #: ###-#### Inspection requested via web by dennis mcneely Dead front needed in exterior panel. 210.63. Recep needed for outdoor A/C equipment
ELE19-00857 Electrical Rough-In3/12/20193/13/20193/13/2019 9:45:08 AMAPASS
Homeowners number ###-#### Phone #: ###-#### Inspection requested via web by Jesse Fuentes Sun room rough in ok to cover
ELE18-04213 Final3/12/20193/13/20193/13/2019 9:35:19 AMAPASS
Garage code is 7352 enter Phone #: ###-#### Inspection requested via web by Zane Robertson corrections made final ok
ELE18-04219 Electrical Rough-In3/12/20193/13/20193/13/2019 9:19:43 AMAPASS
Electrical Inspection for Bonding equal potential and potting Any questions please call Louis at ###-#### Phone #: ###-#### Inspection requested via web by Louis Keller EQ bond and potting ok
ELE16-02584 ELE-Aging Inspection3/13/20193/13/20193/13/2019 8:47:44 AM PASS
Finaled
ELE19-00871 Rough-In Permanent Service3/12/20193/13/20193/13/2019 8:41:32 AMAPASS
Please contact when done Phone #: ###-#### Inspection requested via web by Thomas wilson underground ok to cover p/s u/g rec ok