ELE19-00344
| Conference | 3/13/2019 | 3/13/2019 | 3/13/2019 3:04:31 PM | P | DONE |
|
|
Brian ###-#### Discussed outlet layout in kitchen, and various other locations in home.
|
ELE19-00344
| Electrical Rough-In | 3/12/2019 | 3/13/2019 | 3/13/2019 3:04:00 PM | A | CANC |
|
|
Alright, man. I think I’m ready! Phone #: ###-#### Inspection requested via web by Brad Christensen Changed to a conference.
|
ELE19-00746
| Final | 3/12/2019 | 3/13/2019 | 3/13/2019 3:02:35 PM | P | FAIL |
|
|
New power for paint booth heater. Inside transformer test building. Call David Forbes for access to Idaho Power. Phone #: ###-#### Inspection requested via web by Tod Lane As per article 516 of NEC, any possible ignition point within 3 ft of paint booth opening makes the area a classified location. 4 vent openings to the left of the left door need to be sealed to eliminate hazardous location classification.
|
MIS19-00069
| ELE-Final | 3/13/2019 | 3/13/2019 | 3/13/2019 2:55:46 PM | P | DONE |
|
|
Antonio Phone #: ###-#### Talked to Antonio on phone. Pony wall that was to be built, was not. There is no other electrical associated with this job.
|
ELE19-00876
| Final | 3/13/2019 | 3/13/2019 | 3/13/2019 12:06:22 PM | P | PASS |
|
|
Contact Andrea Richardson Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek Ok final kitchen.
|
ELE19-00825
| Permanent Service | 3/13/2019 | 3/13/2019 | 3/13/2019 11:52:01 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn p/s o/h n ok
|
ELE19-00584
| Electrical Rough-In | 3/13/2019 | 3/13/2019 | 3/13/2019 11:05:36 AM | P | PASS |
|
|
CONTACT: Derrick Kamper Phone #: ###-#### Inspection requested via web by Deb Gooden Ok cover lower plaza. 3 offices and cubicle spaces, bath rooms and kitchen area.
|
ELE19-00005
| Electrical Rough-In | 3/13/2019 | 3/13/2019 | 3/13/2019 11:04:31 AM | P | PASS |
|
|
Contact: Derrick Kamper. Partial cover inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Ok cover conduit NW corner for coffee bar area.
|
ELE19-00842
| Electrical Rough-In | 3/12/2019 | 3/13/2019 | 3/13/2019 10:22:54 AM | A | PASS |
|
|
We will schedule a time to meet you onsite to show you the equipment. Phone #: ###-#### Inspection requested via web by Jesse Simpson Ok cover. Items UL listed.
|
ELE18-04324
| Electrical Rough-In | 3/12/2019 | 3/13/2019 | 3/13/2019 9:45:36 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Brian Gifford Ok cover garage. All wiring in MC. Insulate and sheetrock to be done in the next year or so. Told homeowner he will need another RI inspection before cover.
|
ELE19-00823
| Electrical Rough-In | 3/12/2019 | 3/13/2019 | 3/13/2019 8:51:37 AM | A | PASS |
|
|
The employees at Boise juice have a key to get into the unit to the east of them where you can see I added several circuits and moved the existing panel please call with any questions thanks! Phone #: ###-#### Inspection requested via web by Trevor Soesbe Ok cover N end of unit.
|