Inspections for the day of: Wednesday, March 13, 2019.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-00950 Final3/8/20193/13/20193/13/2019 4:25:14 PMPPASS
Homeowner needs close to 4 as possible, please call when you are on your way Phone #: ###-#### Inspection requested via web by Andrea Grigsby
MEC18-02635 Final3/13/20193/13/20193/13/2019 3:34:28 PMPPASS
Ryan 208 854 9894
- final ok
PLM19-00964 Final3/12/20193/13/20193/13/2019 3:23:04 PMPFAIL
Phone #: ###-#### Inspection requested via web by Floyd Floyd Peek
- water heater needs a disconnect installed with in sight
- water heater drain pan penatrations need sealed
MEC19-00990 Pressure Test3/13/20193/13/20193/13/2019 3:21:34 PMPPASS
GAS LINE CORRECTED AND HOLDING PRESSURE, SORRY FOR THE EXTRA TRIPS. OUTSIDE ACCESS- CALL ME IF YOU HAVE ANY ISSUES- MY NAME IS STEVE DALE- ###-#### Phone #: ###-#### Inspection requested via web by Rick Montgomery
- 20lb gas pressure test ok
- tagged meter location
MEC19-01008 Rough-in3/12/20193/13/20193/13/2019 3:21:10 PMPFAIL
Phone #: ###-#### Inspection requested via web by Floyd Floyd Peek
- new and old line set penetration needs sealed
- A/C fuse size needs to be a 15 amp
MEC19-00839 Final3/13/20193/13/20193/13/2019 2:09:26 PMPPART
Mechanical final needed for today if you have any questions contact Karl at ###-#### thank you. Phone #: ###-#### Inspection requested via web by Karl Hestekin
- waiting on balance report of paint booth
exhaust /make up air
MEC18-05317 Rough-in3/13/20193/13/20193/13/2019 1:37:06 PMPPASS
Light test on grease duct offset and connection to hood. This is ready for a.m., misser the cutoff time. Phone #: ###-#### Inspection requested via web by Drew Tverdy
- light test on offset and hood connection ok
- ok for fire wrap
MEC19-00955 Final3/13/20193/13/20193/13/2019 1:36:15 PMPPASS
Electrical permit has been pulled. Please pass mechanical final. Phone #: ###-#### Inspection requested via web by Arielle Hendricks
-final ok
MEC19-00990 Pressure Test3/12/20193/13/20193/13/2019 10:45:17 AMAFAIL
outside access- line is under pressure and ready to inspect. Call me if you have any questions or concerns, my name is Steve Dale Phone #: ###-#### Inspection requested via web by Rick Montgomery
- gauge under 20lb
MEC19-00820 Final3/12/20193/13/20193/13/2019 10:32:10 AMAPASS
Please call Aaron with any questions. Thanks! Phone #: ###-#### Inspection requested via web by Aaron Shay
- final ok
MEC19-00850 Final3/12/20193/13/20193/13/2019 10:23:55 AMAPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette
- furnace ac coil co ok
MEC19-00361 Final3/12/20193/13/20193/13/2019 10:13:30 AMAPASS
Please call the number provided when on the way. Phone #: ###-#### Inspection requested via web by Steve Bunch
- final ok
MEC19-00943 Final3/7/20193/13/20193/12/2019 2:09:36 PMPCANC
Field super: Chad Robertson Phone #: ###-#### >> Inspection requested via web by Lisa Whitney Inspection cancelled from web by: Lisa Whitney