Inspections for the day of: Friday, March 14, 2003.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00457 FIR-Aging Inspection3/14/20033/14/20033/14/2003 12:00:00 AM NR
Work is almost complete. Waiting for alarm testing 3/14/2003 3:55:12 PM
BLD02-03016 FIRE-Final Inspection3/14/20033/14/20033/14/2003 12:00:00 AMAFAIL
Fire alarm permits required for work performed on the existing fire alarm system. All other life safety items ok
FIR02-00498 INSP-Final Inspection3/11/20033/14/20033/14/2003 12:00:00 AMAFAIL
Still need map as per review note #2 and the lack of a/v's is still an issue 3/14/2003 9:24:04 AM
BLD02-02068 FIRE-Final Inspection3/13/20033/14/20033/14/2003 12:00:00 AMAFAIL
graig; Phone #: ###-#### Provide one additional duct smoke detector and remote alarm LED's for both of them 3/14/2003 12:54:22 PM
FIR03-00058 INSP-Final Inspection3/13/20033/14/20033/14/2003 12:00:00 AMAFAIL
###-#### One sprinkler pendant is blocked by a new cubicle vertical support 3/14/2003 11:02:40 AM
BLD02-03048 FIRE-Final Inspection3/13/20033/14/20033/14/2003 12:00:00 AMAFAIL
###-####. Provide testing and sign off of the fire alarm permit, provide sign off of fire sprinkler permit, fire extinguishers are mounted too high and one is due for reinspection, remove thumbturns on all doors, per general notes on front page of approved drawings all door hardware is to be retrofitted for ADA compliance, repair or replace exit sign at front exit/entry 3/14/2003 12:59:25 PM 3/14/2003 1:00:00 PM
FIR03-00083 INSP-Final Inspection3/13/20033/14/20033/14/2003 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 3/13/2003 at 2:37:58 PM. Contact: ###-####.
FIR02-00213 INSP-Final Inspection3/14/20033/14/20033/14/2003 12:00:00 AMPCANC
###-#### heather (Troy this permit is already finaled...Is that a mistake?) Wrong inspection number. The right number is FIR02-00512 3/14/2003 3:46:52 PM
FIR03-00051 INSP-Final Inspection3/14/20033/14/20033/14/2003 12:00:00 AMPFAIL
provide verification of annual inspection, provide verification that EQ bracing and hangers are per code, provide verification of signage
BLD02-02068 FIRE-Final Inspection3/14/20033/14/20033/14/2003 12:00:00 AMPPART
A temporary occupancy was given with Sam Rogers permission. The contractor needs to add one additional duct smoke detector to a hvac unit over the office area and needs to install a total of two remote alarm LED's. The job superintendant whos name is Graig Durrant signed a letter stating that the above listed work would be completed by Friday, March 21, 2003. All other life safety items are ok.
FIR02-00512 INSP-Final Inspection3/14/20033/14/20033/14/2003 12:00:00 AMPPASS
fire alarm system finaled
FIR03-00112 INSP-Sprinkler Rough-in/Hydro3/14/20033/14/20033/14/2003 12:00:00 AMPPART
One 21' piece of underground pipe is OK to cover. Pipe needed installed so drainage field could be installed