Inspections for the day of: Monday, March 14, 2005.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-00070 Permanent Service3/11/20053/14/20053/14/2005 12:00:00 AMACANC
Alan; Phone #: ###-#### Internet Inspection Request from: Jan Rice ok to final 3/14/2005 8:38:23 AM
ELE05-00821 Temporary Service3/11/20053/14/20053/14/2005 12:00:00 AMAPASS
kevin -###-#### t/s o/h n ok 3/14/2005 9:11:15 AM
ELE05-00808 Permanent Service3/11/20053/14/20053/14/2005 12:00:00 AMAFAIL
Internet Inspection Request from: Lee VanSchoiack 310.16 #8 wire shall be protected by 50A bkr max, BCC job id sticker shall be posted. 3/14/2005 8:13:49 AM
ELE04-02595 Electrical Rough-In3/11/20053/14/20053/14/2005 12:00:00 AMAPART
Chris; Phone #: ###-#### Internet Inspection Request from: Jan Rice ric in elev areas ok, each floor 3/14/2005 10:10:00 AM
ELE05-00070 Final3/14/20053/14/20053/14/2005 12:00:00 AMAPASS
0k to final
ELE04-04012 Final3/14/20053/14/20053/14/2005 12:00:00 AMPPASS
kim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr to add strap to furnace. ok to final 3/14/2005 12:11:32 PM
ELE05-00811 Electrical Rough-In3/11/20053/14/20053/14/2005 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 3/11/2005 at 1:32:57 PM. Contact: ###-####. 680.26(C) Equipotential bonding grid shall be provided and shall extend 3' under paved walking surfaces, BCC job id shall be posted . Called contr, left correction notice 3/14/2005 1:45:13 PM
ELE05-00812 Electrical Rough-In3/11/20053/14/20053/14/2005 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 3/11/2005 at 1:35:56 PM. Contact: ###-####. 680.26(C) Equipotential bonding grid shall be provided and shall extend 3' under paved walking surfaces. BCC job id sticker shall be posted. Called contr, left message about grid, left correction notice 3/14/2005 1:35:25 PM
ELE05-00680 Electrical Rough-In3/14/20053/14/20053/14/2005 12:00:00 AMPPASS
Phone #: ###-#### Internet Inspection Request from: Heather Packer ric walls only center part of office ok 3/14/2005 4:24:16 PM
ELE05-00736 Permanent Service3/14/20053/14/20053/14/2005 12:00:00 AMPPASS
david; Phone #: ###-#### Internet Inspection Request from: Barbara Moore p/s o/h reconnected ok 3/14/2005 3:40:11 PM