ELE05-00070
| Permanent Service | 3/11/2005 | 3/14/2005 | 3/14/2005 12:00:00 AM | A | CANC |
|
|
Alan; Phone #: ###-#### Internet Inspection Request from: Jan Rice ok to final 3/14/2005 8:38:23 AM
|
ELE05-00821
| Temporary Service | 3/11/2005 | 3/14/2005 | 3/14/2005 12:00:00 AM | A | PASS |
|
|
kevin -###-#### t/s o/h n ok 3/14/2005 9:11:15 AM
|
ELE05-00808
| Permanent Service | 3/11/2005 | 3/14/2005 | 3/14/2005 12:00:00 AM | A | FAIL |
|
|
Internet Inspection Request from: Lee VanSchoiack 310.16 #8 wire shall be protected by 50A bkr max, BCC job id sticker shall be posted. 3/14/2005 8:13:49 AM
|
ELE04-02595
| Electrical Rough-In | 3/11/2005 | 3/14/2005 | 3/14/2005 12:00:00 AM | A | PART |
|
|
Chris; Phone #: ###-#### Internet Inspection Request from: Jan Rice ric in elev areas ok, each floor 3/14/2005 10:10:00 AM
|
ELE05-00070
| Final | 3/14/2005 | 3/14/2005 | 3/14/2005 12:00:00 AM | A | PASS |
|
|
0k to final
|
ELE04-04012
| Final | 3/14/2005 | 3/14/2005 | 3/14/2005 12:00:00 AM | P | PASS |
|
|
kim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr to add strap to furnace. ok to final 3/14/2005 12:11:32 PM
|
ELE05-00811
| Electrical Rough-In | 3/11/2005 | 3/14/2005 | 3/14/2005 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 3/11/2005 at 1:32:57 PM. Contact: ###-####. 680.26(C) Equipotential bonding grid shall be provided and shall extend 3' under paved walking surfaces, BCC job id shall be posted . Called contr, left correction notice 3/14/2005 1:45:13 PM
|
ELE05-00812
| Electrical Rough-In | 3/11/2005 | 3/14/2005 | 3/14/2005 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 3/11/2005 at 1:35:56 PM. Contact: ###-####. 680.26(C) Equipotential bonding grid shall be provided and shall extend 3' under paved walking surfaces. BCC job id sticker shall be posted. Called contr, left message about grid, left correction notice 3/14/2005 1:35:25 PM
|
ELE05-00680
| Electrical Rough-In | 3/14/2005 | 3/14/2005 | 3/14/2005 12:00:00 AM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Heather Packer ric walls only center part of office ok 3/14/2005 4:24:16 PM
|
ELE05-00736
| Permanent Service | 3/14/2005 | 3/14/2005 | 3/14/2005 12:00:00 AM | P | PASS |
|
|
david; Phone #: ###-#### Internet Inspection Request from: Barbara Moore p/s o/h reconnected ok 3/14/2005 3:40:11 PM
|