FIR04-00748
| INSP-Supply line flush | 3/11/2005 | 3/14/2005 | 3/14/2005 12:00:00 AM | A | PART |
|
|
Underground hydro test passed. Rough-in failed. Trapeze hangers for the 6" main are overspace. Plans call for 10' max. Provide calcs and spacing requirements for the uni-strut tapeze on the 4" main. Provide verification for head temps at the unit heaters. Backflow preventer in wrong type of manufacturer. Head spacing and pipe size ok. Riser not looked at. 3/14/2005 11:33:22 AM
|
FIR05-00113
| INSP-Sprinkler Rough-in/Hydro | 3/11/2005 | 3/14/2005 | 3/14/2005 12:00:00 AM | A | CANC |
|
|
Trench has not been dug yet. Nothing to inspect. 3/14/2005 9:03:47 AM
|
FIR05-00107
| INSP-Sprinkler Rough-in/Hydro | 3/11/2005 | 3/14/2005 | 3/14/2005 12:00:00 AM | A | PASS |
|
|
Hanger test in the elevator lobby passed. Bill found riser with outdated inspection tag. 3/14/2005 10:52:05 AM
|
FIR05-00091
| INSP-Sprinkler Rough-in | 3/11/2005 | 3/14/2005 | 3/14/2005 12:00:00 AM | A | FAIL |
|
|
Pipe routing has changed and there are alot of added heads. Resubmit plans showing changes and also contractor needs to address the items Bill wanted resubmitted as referenced in the review comments. 3/14/2005 8:48:56 AM
|
BLD04-02661
| FIRE-Final Inspection | 3/11/2005 | 3/14/2005 | 3/14/2005 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled 3/14/2005 2:17:51 PM
|
BLD04-02548
| FIRE-Final Inspection | 3/14/2005 | 3/14/2005 | 3/14/2005 12:00:00 AM | A | PASS |
|
|
Inspection done by Sam Rogers. Fire life safety finaled.
|
BLD04-02090
| FIRE-Final Inspection | 3/14/2005 | 3/14/2005 | 3/14/2005 12:00:00 AM | P | FAIL |
|
|
Provide fire extinguisher as discussed 3/14/2005 4:26:14 PM
|
FIR04-00523
| INSP-Final Inspection | 3/14/2005 | 3/14/2005 | 3/14/2005 12:00:00 AM | P | FAIL |
|
|
Not all of the appliances power shut off. Manual pulls have been relocated and operate correctly 3/14/2005 4:25:44 PM
|
BLD04-02708
| FIRE-Final Inspection | 3/14/2005 | 3/14/2005 | 3/14/2005 12:00:00 AM | P | FAIL |
|
|
dave ###-#### Provide fire extinguisher per review comment #4, Provide additional exit signs as per drawing sheet #A2.3 and provide emergency lighting in north side of elevator lobby and in both exit corridors. 3/14/2005 2:19:27 PM
|
MIS05-00029
| FIR-Final | 3/14/2005 | 3/14/2005 | 3/14/2005 12:00:00 AM | P | PART |
|
|
###-#### bill basham Mount fire extinguisher in a normal path of travel with the handle at 48" above AFF with annual inspection tag. Provide approved door hardware on both west end north and south facing exit doors. Lever hardware is ok. Remove the thumbturn lock from the north facing east door. 3/14/2005 1:58:24 PM
|