Inspections for the day of: Monday, March 14, 2005.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00748 INSP-Supply line flush3/11/20053/14/20053/14/2005 12:00:00 AMAPART
Underground hydro test passed. Rough-in failed. Trapeze hangers for the 6" main are overspace. Plans call for 10' max. Provide calcs and spacing requirements for the uni-strut tapeze on the 4" main. Provide verification for head temps at the unit heaters. Backflow preventer in wrong type of manufacturer. Head spacing and pipe size ok. Riser not looked at. 3/14/2005 11:33:22 AM
FIR05-00113 INSP-Sprinkler Rough-in/Hydro3/11/20053/14/20053/14/2005 12:00:00 AMACANC
Trench has not been dug yet. Nothing to inspect. 3/14/2005 9:03:47 AM
FIR05-00107 INSP-Sprinkler Rough-in/Hydro3/11/20053/14/20053/14/2005 12:00:00 AMAPASS
Hanger test in the elevator lobby passed. Bill found riser with outdated inspection tag. 3/14/2005 10:52:05 AM
FIR05-00091 INSP-Sprinkler Rough-in3/11/20053/14/20053/14/2005 12:00:00 AMAFAIL
Pipe routing has changed and there are alot of added heads. Resubmit plans showing changes and also contractor needs to address the items Bill wanted resubmitted as referenced in the review comments. 3/14/2005 8:48:56 AM
BLD04-02661 FIRE-Final Inspection3/11/20053/14/20053/14/2005 12:00:00 AMAPASS
Fire life safety finaled 3/14/2005 2:17:51 PM
BLD04-02548 FIRE-Final Inspection3/14/20053/14/20053/14/2005 12:00:00 AMAPASS
Inspection done by Sam Rogers. Fire life safety finaled.
BLD04-02090 FIRE-Final Inspection3/14/20053/14/20053/14/2005 12:00:00 AMPFAIL
Provide fire extinguisher as discussed 3/14/2005 4:26:14 PM
FIR04-00523 INSP-Final Inspection3/14/20053/14/20053/14/2005 12:00:00 AMPFAIL
Not all of the appliances power shut off. Manual pulls have been relocated and operate correctly 3/14/2005 4:25:44 PM
BLD04-02708 FIRE-Final Inspection3/14/20053/14/20053/14/2005 12:00:00 AMPFAIL
dave ###-#### Provide fire extinguisher per review comment #4, Provide additional exit signs as per drawing sheet #A2.3 and provide emergency lighting in north side of elevator lobby and in both exit corridors. 3/14/2005 2:19:27 PM
MIS05-00029 FIR-Final3/14/20053/14/20053/14/2005 12:00:00 AMPPART
###-#### bill basham Mount fire extinguisher in a normal path of travel with the handle at 48" above AFF with annual inspection tag. Provide approved door hardware on both west end north and south facing exit doors. Lever hardware is ok. Remove the thumbturn lock from the north facing east door. 3/14/2005 1:58:24 PM