Inspections for the day of: Tuesday, March 14, 2006.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-04493 ELE-Aging Inspection3/14/20063/14/20063/16/2006 1:28:25 PM FAIL
corr. posted called 352.1,2,46 needs connector where RNC enters sign enclosure, 600.5(C)(3) & 410.15(B)(1,2)(3 a,b) shall provide handhole opposite of threaded nipple with grd terminal accsecible at handhole in the pole as codes noted states note this is for sign at 6909 fairview address permit address was wrong, under 8655 fairview address
ELE06-00711 Electrical Rough-In3/13/20063/14/20063/14/2006 4:16:32 PMPCANC
Scheduled by a contractor via Hello! on 3/13/2006 at 3:27:42 PM. Contact: ###-####. will do 03-15-06 in the AM
ELE06-00839 Temporary Service3/10/20063/14/20063/14/2006 4:15:21 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson t/s u/g new ok
ELE06-00822 Temporary Service3/14/20063/14/20063/14/2006 4:14:56 PMPPASS
dino; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa t/s u/g new ok
ELE06-00863 Temporary Service3/14/20063/14/20063/14/2006 3:01:16 PMPPASS
Rhonda -- reinspection; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong t/s u/g new ok
ELE06-00872 Electrical Rough-In3/14/20063/14/20063/14/2006 2:19:24 PMPFAIL
###-#### - Jack Dillard Note: please call 1/2 prior to inspection corr. called 210.52(B) din rm shall be on small appliance branch circuit
ELE06-00842 Electrical Rough-In3/14/20063/14/20063/14/2006 1:38:55 PMPPART
George -- reinspection; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong walls ok corr. posted for ceiling, and no violations to be retained, use manufactures listed breakers only shall not support low voltage cables from conduit, remove abandoned low voltage cables, needs conn. or bushings for phone emt not couplings abrasions protection called
ELE06-00772 Rough-In Permanent Service3/14/20063/14/20063/14/2006 12:52:24 PMPFAIL
permit has been changed to show 400 amp service. Thank you!; Phone #: ###-#### Internet Inspection Request from: William Zerfas corr. called 110.26(F)(1) remove phone and catv cable from below p/s, 250.64(C) shall not splice GEC in neutral bus shall be continuious
ELE05-04665 Final3/13/20063/14/20063/14/2006 10:47:52 AMAPASS
Charlie Internet Inspection Request from: Melyne Davis ok
ELE06-00772 Rough-In Permanent Service3/13/20063/14/20063/14/2006 10:18:36 AMAFAIL
The service at this job has been changed from a 200amp to a 325amp. If changes on permit need to be made and we owe $, please do so and let me know! Thank you!; Phone #: ###-#### Internet Inspection Request from: William Zerfas
corr. do not cover, called 250.24(A)(1) terminate GEC too bus or terminal neutral is terminated to, needs to update permit for 400 amp service, shall have only one range cable remove the extra one bld permit states no duplex or ADU people are trying to build the house with a apartent in the back of the house
ELE06-00433 Final3/13/20063/14/20063/14/2006 9:48:02 AMAPASS
Call Steve Ruter ###-####; Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson ok card signed corr. made
ELE05-04498 ELE-Aging Inspection3/14/20063/14/20063/14/2006 9:38:00 AM PART
called wsuc
ELE06-00842 Electrical Rough-In3/13/20063/14/20063/14/2006 9:28:36 AMANH
Scheduled by a contractor via Hello! on 3/13/2006 at 7:18:10 PM. Contact: ###-####. notice posted called
ELE06-00837 Final3/13/20063/14/20063/14/2006 8:52:38 AMAPASS
We installed a new 30 amp 4 wire dryer circuit with new receptacle.(#6030236tweede)Jason###-####.Thanks!!! Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok
ELE06-00863 Temporary Service3/13/20063/14/20063/14/2006 8:10:30 AMAFAIL
Rhonda; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
corr. posted called 250.24(A)(1), terminate grd to neutral bus, 312.5 conn. for GEC