Inspections for the day of: Tuesday, March 14, 2006.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-04488 ELE-Aging Inspection3/14/20063/14/20063/16/2006 8:19:46 AM DONE
see final
ELE05-04598 Final3/14/20063/14/20063/14/2006 4:32:24 PMPPASS
ron; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final
ELE06-00274 Final3/14/20063/14/20063/14/2006 4:22:47 PMPPASS
Sean; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ok to final
ELE05-04259 Final3/14/20063/14/20063/14/2006 3:13:36 PMPNR
Scheduled by a contractor via Hello! on 3/14/2006 at 6:01:30 AM. Contact: ###-####. elect was held up, told to re-call
ELE06-00866 Electrical Rough-In3/14/20063/14/20063/14/2006 2:59:24 PMPPASS
charlie Internet Inspection Request from: Melyne Davis ric ok
ELE06-00875 Electrical Rough-In3/14/20063/14/20063/14/2006 2:49:30 PMPFAIL
lloyd ###-#### called cont, left corr notice, 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members, 210.11(C) kitchen shall be supplied with at least 2 20a small appliance branch circuits for recpt outlets,210.52(C)(1) recpt outlets shall be installed so that no point along the wall line is more than 24" from an outlet( by sink), 410.16(A) outlet box shall be installed to support luminaire
ELE06-00657 Electrical Rough-In3/10/20063/14/20063/14/2006 1:09:20 PMPPASS
1st Floor - Sign Shop; Phone #: ###-#### Internet Inspection Request from: Celinda Winters walls and shop ceiling ok to cover
ELE05-02631 Permanent Service3/10/20063/14/20063/14/2006 1:07:59 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Celinda Winters p/s u/g n ok
ELE06-00819 Permanent Service3/14/20063/14/20063/14/2006 12:07:28 PMPPASS
roy ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie p/s u/g n ok
ELE05-04467 Final3/13/20063/14/20063/14/2006 11:41:45 AMAFAIL
please look at trench work also///Phone #: ###-#### Internet Inspection Request from: todd hall called contr, left corr notice,210.63, shall provide 125 v single phase recpt (gfci) for rooftop, 300.5 u/g shall be 24" under drive, 110.3(B) gfci shall operate,408.4 panel sched shall be complete
ELE05-04411 Final3/13/20063/14/20063/14/2006 11:39:01 AMAFAIL
vivian; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr, left corr notice, 110.12(C) service panel door shall operate and access shall be available,entry and back shall be accessible. rest of house ok
ELE06-00089 Final3/13/20063/14/20063/14/2006 10:56:48 AMAPASS
access code 3174; Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS called, left survey, 352.30 rnc shall be strapped within 3' of panel,440.4 a/c shall be protected by nameplate data
ELE06-00858 Final3/13/20063/14/20063/14/2006 10:53:12 AMACANC
final inspection on hot tub installation. call Bill Wozniak for access @ ###-####. thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called contr, told them can't do inspection until we see u/g
ELE05-04639 Electrical Rough-In3/13/20063/14/20063/14/2006 8:33:48 AMAPASS
CONTACT: MIKE ROBINSON - CEILING INSPECTION; Phone #: ###-#### Internet Inspection Request from: Deb McCoy called contr to tie a few ceiling support wires top and bottom, ceiling cover ok
ELE06-00113 Electrical Rough-In3/10/20063/14/20063/14/2006 8:16:40 AMAPART
CONTACT: LYLE DEAN - ROUGH IN INSPECTION 6TH FLOOR; Phone #: ###-#### Internet Inspection Request from: Deb McCoy walls only anop,6th fl
ELE06-00819 Final3/14/20063/14/20063/14/2006 12:00:00 AMPPASS
ok to final
ELE05-02001 Final3/14/20063/14/20063/14/2006 12:00:00 AMPPASS
ok to final
ELE05-04308 Final3/14/20063/14/20063/14/2006 12:00:00 AMPPASS
ok to final