Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00193 INSP-Final Inspection3/13/20063/14/20063/15/2006 12:38:11 AMPPASS
Items on c/n have been completed, signals verified, EOL tested, inspection passed. Permit finaled.
FIR05-00192 INSP-Final Inspection3/13/20063/14/20063/15/2006 12:36:43 AMPPASS
c/n items have been completed, EOL's tested, signals verified, inspection passed. Permit finaled.
FIR06-00132 INSP-Final Inspection3/13/20063/14/20063/14/2006 5:00:51 PMADEFR
Inspection to be rescheduled per phone conversation with contractor.
FIR06-00170 INSP-Final Inspection3/13/20063/14/20063/14/2006 4:17:14 PMAPASS
The hood suppression system operated correctly under test conditions, the provided K class extinguisher to be lowered to the proper height AFF as discussed.
FIR05-00659 INSP-Sprinkler Rough-in/Hydro3/14/20063/14/20063/14/2006 3:40:18 PMPCANC
Per S. Rogers, no field inspection is to be performed until the required resubmitted plans are stamped/approved and on site for verification of code compliance.
FIR05-00840 INSP-Sprinkler Rough-in3/14/20063/14/20063/14/2006 3:36:19 PMPFAIL
Pendent heads at the remainder of the vacant floor area have been changed to quick response, however no drop ceiling is installed, heads are at various heights AFF, spacing is irregular, final pending compliance with the upgrade agreement per permit review notes.
BLD01-01632 FIRE-Final Inspection3/13/20063/14/20063/14/2006 3:30:19 PMAPASS
c/n items are complete, delayed egress locks tested and verified for sequence of operation and functionality, emergency lighting tested, inspection passed, fire life safety is acceptable.
BLD05-03099 FIRE-Final Inspection3/13/20063/14/20063/14/2006 12:27:41 PMAPASS
Fire life safety passed inspection, surface bolt hardware at the back door removed while on site.
FIR05-00892 INSP-Final Inspection3/14/20063/14/20063/14/2006 12:22:48 PMPPASS
Ceiling tile and escutcheons have been installed, fire sprinkler permit finaled.
FIR06-00012 INSP-Sprinkler Rough-in/Hydro3/13/20063/14/20063/14/2006 11:49:35 AMAPART
Overhead hydrostatic test is satisfactory, overhead rough-in is good for cover, missing hanger retaining strap at one location installed while on site, final pending ceiling and escutcheons.
BLD05-01077 FIRE-Final Inspection3/13/20063/14/20063/14/2006 11:13:44 AMAFAIL
Life safety Inspection for the parking structure ground level, 2nd, and 3rd floors for temp. occupancy failed due to non-functional emergency lights at the 2nd and 3rd levels, fire extinguishers at two locations are mounted too high, minor fire sprinkler issues,emergency lighting at stair #3 not tested, fire apparatus access roads must meet requirements of IFC 2003 503.2.1 and 503.4.
FIR05-00594 INSP-Supply line flush3/13/20063/14/20063/14/2006 10:57:50 AMADEFR
This inspection request was intended for an UG supply line flush under project related permit FIR05-00395-contractor called in the wrong permit number (for overhead), flush was witnessed and performed satisfactory.
FIR05-00817 INSP-Final Inspection3/13/20063/14/20063/14/2006 10:53:28 AMAPASS
Items on the previous correction notice have been completed, fire sprinkler permit finaled.
BLD05-02316 FIRE-Final Inspection3/14/20063/14/20063/14/2006 12:00:00 AMPCANC
michael evans; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa rescheducled