Inspections for the day of: Wednesday, March 14, 2007.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-00868 Permanent Service3/14/20073/14/20073/14/2007 6:03:24 PMPPASS
p/s o/h rec. ok
corr. posted shall isolate grds and neutrals at sub panel today , other violations shall be corrected first thing 03-15-07 AM range&dryer shall have 4 wire recepts and pigtails installed, use manufactures breakers only install conn. on all cables, needs machine screws for equip grd bus, remove 10/2 circuit from dryer breaker and find out its purpose, label panel be specific,
note if not done power will be disconnected until corrections are made
ELE07-00046 Electrical Rough-In3/14/20073/14/20073/14/2007 2:48:44 PMPFAIL
harven; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles same coorections as before over 360 degrees of bends in conduit, and job not ready
ELE06-03623 Final3/13/20073/14/20073/14/2007 2:00:47 PMPFAIL
jeremy ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
nr needs labels for recepts (no equip. grd) shall not use 90 degree flex fittings for romex, complete all wiring, panel directories shall be specific
ELE07-00781 Permanent Service3/14/20073/14/20073/14/2007 12:55:52 PMPPASS
RIchard. early as possible.; Phone #: ###-#### Internet Inspection Request from: Stacie Backus p/s o/h rec. ok
ELE06-02053 Final3/14/20073/14/20073/14/2007 12:40:09 PMPPASS
mike ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok
ELE07-00465 Electrical Rough-In3/13/20073/14/20073/14/2007 12:17:14 PMACANC
This is a ceiling inspection. Phone #: ###-#### contractor canceled
ELE07-00814 Rough-In Permanent Service3/14/20073/14/20073/14/2007 10:54:19 AMAFAIL
Scheduled by a contractor via Hello! on 3/14/2007 at 5:19:56 AM. Contact: ###-####. corr called 210.52 needs outlet kit wall by pantry, also by fixed panel of slider, 410.8 clearence closet fixtures
ELE06-04594 Electrical Rough-In3/13/20073/14/20073/14/2007 10:22:12 AMANR
russ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles box fill, nail plates , protect romex run horizontal in unfinished walls, isolate grds and neuts at panel use plastic conn for GEC
ELE06-04116 Final3/13/20073/14/20073/14/2007 9:19:56 AMAPASS
steve; Phone #: ###-#### Internet Inspection Request from: Stacie Backus
ELE07-00036 Final3/14/20073/14/20073/14/2007 8:47:39 AMAPASS
Call for accesss. Please call if there are any questions or problems. Thank You Phone #: ###-#### ok
ELE07-00035 Final3/14/20073/14/20073/14/2007 8:47:19 AMAPASS
Call for access. Please call if there are any questions or problems. Thank You Phone #: ###-#### ok