ELE07-00697
| Final | 3/14/2007 | 3/14/2007 | 3/14/2007 3:33:50 PM | P | PASS |
|
|
ok to final
|
ELE06-04726
| Permanent Service | 3/14/2007 | 3/14/2007 | 3/14/2007 3:25:24 PM | P | FAIL |
|
|
Permanent Service Inspection, call Steve Ruter ###-#### Phone #: ###-#### called contr, BCC code, no address on bldg or property
|
ELE07-00848
| Electrical Rough-In | 3/13/2007 | 3/14/2007 | 3/14/2007 2:48:30 PM | P | PASS |
|
|
can you call before going over there so I can make sure that I am there. Thanks Phone #: ###-#### ric ok
|
ELE07-00842
| Permanent Service | 3/13/2007 | 3/14/2007 | 3/14/2007 1:41:24 PM | A | PASS |
|
|
bill - 2pm; Phone #: ###-#### Internet Inspection Request from: Victoria Beall p/s o/h rec ok, will build platform and call for final ltr
|
ELE06-04004
| Final | 3/14/2007 | 3/14/2007 | 3/14/2007 1:23:21 PM | P | FAIL |
|
|
duane ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith told people would leave corr notice, nec300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 314.17(C) nm cable shall be stapled within 8" of box, 230.24(A) service conductors shall be 8' above roof surface, 250.64(C) gec shall not be spliced, 250.52(A)(3) shall use concrete encased electrode, 312.5 all conductors entering enclosures shall have abrasion protection,240.4 conductors shall be protected against overcurrent according to their ampacity specified in 310.15, BCC all make-up shall be done and inspected prior to device installation
|
ELE05-00490
| Electrical Rough-In | 3/13/2007 | 3/14/2007 | 3/14/2007 12:44:54 PM | P | PASS |
|
|
steve ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ric garage ok
|
ELE07-00857
| Permanent Service | 3/14/2007 | 3/14/2007 | 3/14/2007 12:44:14 PM | P | PASS |
|
|
allen Note: garage no meter - coming from the existing house service ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s ok
|
ELE05-02303
| Electrical Rough-In | 3/13/2007 | 3/14/2007 | 3/14/2007 10:15:14 AM | A | PASS |
|
|
Larry; Phone #: ###-#### Internet Inspection Request from: Stacie Backus corr made, ric ok
|
ELE07-00809
| Electrical Rough-In | 3/12/2007 | 3/14/2007 | 3/14/2007 9:44:24 AM | A | PASS |
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to cover u/g conduit only - verify whole area has concrete slab
|
ELE07-00503
| Electrical Rough-In | 3/13/2007 | 3/14/2007 | 3/14/2007 9:11:46 AM | A | PASS |
|
|
Inspection to backfill conduit inside foundation Phone #: ###-#### ok to backfill conduit inside foundation only
|
ELE07-00114
| Final | 3/13/2007 | 3/14/2007 | 3/14/2007 8:53:22 AM | A | PASS |
|
|
Phone #: ###-#### corrections made, ok to final, signed occ card
|
ELE07-00693
| Electrical Rough-In | 3/14/2007 | 3/14/2007 | 3/14/2007 8:35:20 AM | A | PASS |
|
|
Bob, just the outside sofits, front and back we need O.K. to cover. Thanks. Joe Phone #: ###-#### ok to cover soffits, called to ensure stapling nm cable
|