Inspections for the day of: Wednesday, March 14, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-00697 Final3/14/20073/14/20073/14/2007 3:33:50 PMPPASS
ok to final
ELE06-04726 Permanent Service3/14/20073/14/20073/14/2007 3:25:24 PMPFAIL
Permanent Service Inspection, call Steve Ruter ###-#### Phone #: ###-#### called contr, BCC code, no address on bldg or property
ELE07-00848 Electrical Rough-In3/13/20073/14/20073/14/2007 2:48:30 PMPPASS
can you call before going over there so I can make sure that I am there. Thanks Phone #: ###-#### ric ok
ELE07-00842 Permanent Service3/13/20073/14/20073/14/2007 1:41:24 PMAPASS
bill - 2pm; Phone #: ###-#### Internet Inspection Request from: Victoria Beall p/s o/h rec ok, will build platform and call for final ltr
ELE06-04004 Final3/14/20073/14/20073/14/2007 1:23:21 PMPFAIL
duane ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith told people would leave corr notice, nec300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 314.17(C) nm cable shall be stapled within 8" of box, 230.24(A) service conductors shall be 8' above roof surface, 250.64(C) gec shall not be spliced, 250.52(A)(3) shall use concrete encased electrode, 312.5 all conductors entering enclosures shall have abrasion protection,240.4 conductors shall be protected against overcurrent according to their ampacity specified in 310.15, BCC all make-up shall be done and inspected prior to device installation
ELE05-00490 Electrical Rough-In3/13/20073/14/20073/14/2007 12:44:54 PMPPASS
steve ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ric garage ok
ELE07-00857 Permanent Service3/14/20073/14/20073/14/2007 12:44:14 PMPPASS
allen Note: garage no meter - coming from the existing house service ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s ok
ELE05-02303 Electrical Rough-In3/13/20073/14/20073/14/2007 10:15:14 AMAPASS
Larry; Phone #: ###-#### Internet Inspection Request from: Stacie Backus corr made, ric ok
ELE07-00809 Electrical Rough-In3/12/20073/14/20073/14/2007 9:44:24 AMAPASS
jim; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to cover u/g conduit only - verify whole area has concrete slab
ELE07-00503 Electrical Rough-In3/13/20073/14/20073/14/2007 9:11:46 AMAPASS
Inspection to backfill conduit inside foundation Phone #: ###-#### ok to backfill conduit inside foundation only
ELE07-00114 Final3/13/20073/14/20073/14/2007 8:53:22 AMAPASS
Phone #: ###-#### corrections made, ok to final, signed occ card
ELE07-00693 Electrical Rough-In3/14/20073/14/20073/14/2007 8:35:20 AMAPASS
Bob, just the outside sofits, front and back we need O.K. to cover. Thanks. Joe Phone #: ###-#### ok to cover soffits, called to ensure stapling nm cable