BLD05-00454
| FIRE-Final Inspection | 3/14/2007 | 3/14/2007 | 3/15/2007 11:31:41 AM | P | FAIL |
|
|
Smoke alarms need to be relocated to atleast 3' away from the bathroom doors. All other items are ok.
|
BLD05-00453
| FIRE-Final Inspection | 3/14/2007 | 3/14/2007 | 3/15/2007 11:30:12 AM | P | FAIL |
|
|
Smoke alarms need to be relocated to atleast 3' away from the bathroom doors. All other items are ok.
|
FIR06-00958
| INSP-Sprinkler Rough-in/Hydro | 3/14/2007 | 3/14/2007 | 3/15/2007 11:27:32 AM | P | PASS |
|
|
The remaining underground supply and FDC piping is ok to cover. Both passed their hydro testes
|
FIR07-00081
| INSP-Final Inspection | 3/14/2007 | 3/14/2007 | 3/14/2007 2:54:17 PM | P | DONE |
|
|
Conference was for the storage room. The existing wall mounted device is blocked by product on the shelf and by the storage rack in the middle of the room. I agreed with steve that a ceiling mounted device would be adequate as long as the kept the storage 18" below the ceiling as per code. That way the ceiling mounted device would be viewable in all areas.
|
BLD06-01234
| FIRE-Final Inspection | 3/14/2007 | 3/14/2007 | 3/14/2007 2:17:39 PM | P | FAIL |
|
|
Sprinkler heads are overspace in two of the new offices and one pendant is overspaced outside fo the new offices at the east wall. A sprinkler permit will be required for this work. Life safety will be ok to final when sprinkler work is complete.
|
BLD06-01234
| FIRE-Sprinkler Rough-in | 3/14/2007 | 3/14/2007 | 3/14/2007 2:17:05 PM | P | FAIL |
|
|
Sprinkler heads are overspace in two of the new offices and one pendant is overspaced outside fo the new offices at the east wall. A sprinkler permit will be required for this work. Life safety will be ok to final when sprinkler work is complete.
|
FIR07-00121
| INSP-Sprinkler Rough-in/Hydro | 3/13/2007 | 3/14/2007 | 3/14/2007 11:35:38 AM | A | PASS |
|
|
Sprinkler piping is ok to cover but one hanger infront of the refrigerator is attached to duct work and will need to be relocated to the building structure.
|