Inspections for the day of: Wednesday, March 14, 2012.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS12-00047 FIR-Conference3/14/20123/14/20123/14/2012 3:17:57 PMPDONE
I spoke to Jesse on the phone while at the job site and he stated that the fire hydrant has not been installed yet. I told him I would follow up in three weeks.
FIR11-00607 INSP-Sprinkler Rough-in3/14/20123/14/20123/14/2012 2:55:38 PMPPASS
The sprinkler piping above the lay-in tile areas can be covered.
BLD12-00167 FIRE-Final Inspection3/13/20123/14/20123/14/2012 2:32:16 PMAFAIL
Provide inspection for the hood suppression system, remove the dead bolt and provide lever hardware on the kitchen exit door, resubmit floor plan that matches the actual wall layout.
BLD11-01395 FIRE-Final Inspection3/13/20123/14/20123/14/2012 11:40:33 AMAPASS
life safety passed
BLD11-03003 FIRE-Final Inspection3/13/20123/14/20123/14/2012 11:31:25 AMAPASS
life safety passed. wire shelving is provided
BLD11-01652 FIRE-Final Inspection3/14/20123/14/20123/14/2012 11:29:17 AMPPASS
life safety passed
BLD11-01364 FIRE-Final Inspection3/13/20123/14/20123/14/2012 11:27:26 AMACANC
No required sign off for life safety.
FIR12-00023 INSP-Alarm Testing3/13/20123/14/20123/14/2012 9:04:38 AMAFAIL
A strobe in the basement stairwell is overspaced. It originally had a symbol designation for the candella rating and no one knew what it stood for. The contractor installed a 15cd in its place prior to this inspection. This 15cd strobe is overspace for corridor spacing and for room spacing. It was agreed that a 75cd strobe would work and will be installed. As builts do not match the installation and will need to be revised. Still need to witness the sync'ing of the audio/visual devices and verify EOL. I offered to perform both of these services but my offer was declined due to the 15cd strobe issue and an acceptable way to verify the EOL not being agreed upon yet. A re-inspection fee as been assigned.