Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00011 INSP-Sprinkler Rough-in3/11/20133/12/2013 P 
This is for the 3rd, 4th & 5th Fl. Mike B is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus
FIR13-00011 INSP-Sprinkler Rough-in3/13/20133/14/20133/14/2013 5:33:03 PMPPART
6th floor rough-in completed. Noted missing coverage at the SE corner, beam obstruction at the fire service elevator lobby.
BLD13-00055 FIRE-Final Inspection3/14/20133/14/20133/14/2013 5:27:07 PMPFAIL
Missing exit signs per plan red-lines, provide EM lighting at the new door, must meet IFC conditions for delayed egress.
BLD13-00175 FIRE-Final Inspection3/13/20133/14/20133/14/2013 5:24:41 PMAFAIL
Provide "door to remain unlocked.." signage at the main entry/exit, post one 2A10BC rated fire extinguisher, provide current certification for the K class PFE. Existing type one hood appears overdue inspection, nozzles do not match equipment layout- enclosed pizza oven only.