ELE11-02641
| Final | 3/14/2013 | 3/14/2013 | 3/14/2013 4:40:22 PM | P | PASS |
|
|
Repair underground branch circuit to sign. final ok
|
ELE11-01900
| ELE-Aging Inspection | 3/14/2013 | 3/14/2013 | 3/14/2013 3:19:41 PM | | DONE |
|
|
still undeer construction
|
ELE13-00567
| Rough-In Permanent Service | 3/14/2013 | 3/14/2013 | 3/14/2013 3:05:11 PM | P | FAIL |
|
|
Will be unlocked. Thanx Phone #: ###-#### >> Inspection requested via web by Clay Morgan NEC300.4 nail plates required in kitchen. NEC 334.30 shall secure NM cable within 12 inches of entering service panel. NEC 310.15(B)(2) Derating of (20) current carrying conductors in a raceway
|
ELE13-00556
| Final | 3/14/2013 | 3/14/2013 | 3/14/2013 2:25:03 PM | P | PASS |
|
|
Job complete final ok
|
ELE12-02915
| Final | 3/14/2013 | 3/14/2013 | 3/14/2013 2:24:04 PM | P | PASS |
|
|
kurt Phone #: ###-#### - before 3 if possible - call prior to going No tub in master bathroom at time of final final ok
|
ELE13-00556
| Electrical Rough-In | 3/13/2013 | 3/14/2013 | 3/14/2013 2:04:33 PM | P | PASS |
|
|
Contact is Jason Gaythwaite Phone #: ###-#### >> Inspection requested via web by Kelly Felin rough-in ok
|
ELE13-00393
| Rough-In Permanent Service | 3/14/2013 | 3/14/2013 | 3/14/2013 1:51:34 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson rough-in p/s u/g n ok Advised electrical contractor of his live temporary power pole laying on the ground with unfused conductors exposed,
|
ELE12-02726
| Permanent Service | 3/14/2013 | 3/14/2013 | 3/14/2013 1:05:49 PM | P | PASS |
|
|
max Phone #: ###-#### p/s u/g n ok
|
ELE13-00345
| Final | 3/13/2013 | 3/14/2013 | 3/14/2013 10:19:14 AM | A | PASS |
|
|
Please call Butch prior to Inspection. Thank you! Phone #: ###-#### >> Inspection requested via web by Daniel Schaffeld final ok
|
ELE12-02798
| Final | 3/13/2013 | 3/14/2013 | 3/14/2013 9:51:40 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Not ready for final inspection
|
ELE13-00221
| Final | 3/13/2013 | 3/14/2013 | 3/14/2013 9:33:20 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by David Baker UL ;listed sign final ok
|
ELE13-00546
| Final | 3/13/2013 | 3/14/2013 | 3/14/2013 9:26:00 AM | A | PASS |
|
|
HP. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy No C of O card on site final ok
|
ELE13-00263
| Electrical Rough-In | 3/13/2013 | 3/14/2013 | 3/14/2013 8:42:16 AM | A | PASS |
|
|
2nd floor soffit cans 7 total Phone #: ###-#### >> Inspection requested via web by Patrick D Gill rough-in ok cover
|