MEC17-00942
| Rough-in | 3/14/2017 | 3/14/2017 | 3/14/2017 2:28:37 PM | P | FAIL |
|
|
Tech. Patrick ###-#### Phone #: ###-#### Inspection requested via web by SOPHIA FLEMING need approved manual j on site for rough-in inspection
|
MEC17-00942
| Pressure Test | 3/14/2017 | 3/14/2017 | 3/14/2017 2:27:40 PM | P | PASS |
|
|
Tech. Patrick ###-#### Phone #: ###-#### Inspection requested via web by SOPHIA FLEMING 20lb gas, 5lb flue
|
MEC17-00897
| Final | 3/10/2017 | 3/14/2017 | 3/14/2017 1:59:13 PM | P | NH |
|
|
Pre-call technician Scott at ###-#### 30-45 minutes prior to arrival. Phone #: ###-#### Inspection requested via web by Andrea Grigsby
|
MEC16-04908
| Final | 3/13/2017 | 3/14/2017 | 3/14/2017 1:39:53 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves need air balance report, armaflex needs uv protection
|
MEC17-00435
| Rough-in | 3/14/2017 | 3/14/2017 | 3/14/2017 1:15:05 PM | P | PASS |
|
|
2nd floor soffits Phone #: ###-#### Inspection requested via web by Crystal Grant 2nd floor soffits pod1
|
MEC17-00895
| Rough-in | 3/13/2017 | 3/14/2017 | 3/14/2017 9:29:09 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ed Ables
|
MEC17-00887
| Rough-in | 3/13/2017 | 3/14/2017 | 3/14/2017 9:12:08 AM | A | PART |
|
|
Phone #: ###-#### Inspection requested via web by Krista Boss dryer vent needs nailplate at the floor, exhaust fans need to be in for rough-in
|
MEC17-00887
| Pressure Test | 3/13/2017 | 3/14/2017 | 3/14/2017 9:11:06 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Krista Boss 5lb flue
|
MEC16-03630
| Mec-Aging Inspection | 3/14/2017 | 3/14/2017 | 3/14/2017 8:14:14 AM | | PEND |
|
|
still working
|
MEC16-03629
| Mec-Aging Inspection | 3/14/2017 | 3/14/2017 | 3/14/2017 8:13:12 AM | | PEND |
|
|
|