Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-01608 Final3/14/20183/14/20183/14/2018 2:10:20 PMPPASS
James Phone #: ###-####
Final ok
ELE18-00027 Final3/14/20183/14/20183/14/2018 1:59:50 PMPFAIL
Justin Metcalf ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg
210.8- All receptacles located within 6' of a sink shall have GFCI protection. Break rm.
* Complete lighting, several pendants yet to hang. Several receptacles not working, 1/2 wall and conference room.
Recall when complete.
ELE18-00278 Final3/13/20183/14/20183/14/2018 10:47:43 AMAPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Final ok
ELE17-04203 Final3/13/20183/14/20183/14/2018 10:11:29 AMAPASS
Final for Basement. Please call Travis with Vertical Construction when on your way or to schedule a time so he can let you in.
###-#### Phone #: ###-#### Inspection requested via web by Cyndi Dale Final ok
ELE18-00900 Conference3/9/20183/14/20183/14/2018 9:47:59 AMADONE
I will be on site by 8:30 am. Feel free to call me when you are on your way and I will meet you at the front door. Phone #: ###-#### Inspection requested via web by Craig Korell
Discussed the requirements for pool remodel. Pool shell bonding will be bonded to exposed rebar and then rebar will be encased in new concrete pour. 6" of concrete to be added to top of pool shell with seperate bond needed due to this rebar not connected to existing. Equipotential perimeter bond and new LED luminaires to be installed in existing luminaire shells. Bonding and potting inspections required for lighting. All pool equipment to be GFCI protected.
ELE18-00901 Permanent Service3/13/20183/14/20183/14/2018 8:51:51 AMAPASS
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
p/s u/g n ok
ELE18-00901 Electrical Rough-In3/13/20183/14/20183/14/2018 8:51:22 AMAPASS
ug conduit Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
Midway between road and house underground rough in ok cover