Inspections for the day of: Wednesday, March 14, 2018.
Number of inspections: 23
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-01169 Pressure Test3/13/20183/14/20183/14/2018 4:01:34 PMPFAIL
PM. Please call when on way. Gener ###-####. Phone #: ###-#### Inspection requested via web by Krista Boss- gauge wont zero out
MEC18-01126 Final3/14/20183/14/20183/14/2018 3:39:55 PMPPASS
If you could please call Bob H when heading over. Thank you! ###-#### Phone #: ###-#### Inspection requested via web by Ron Arnold
MEC18-01133 Rough-in3/14/20183/14/20183/14/2018 3:07:04 PMPFAIL
Phone #: ###-#### Inspection requested via web by Randy Hart- all exhaust fans need taped/sealed where ties onto fan- b vent at roof level furnace location needs 1" clearance to combustibles and pipe secured- corretion notice front window
MEC18-01134 Rough-in3/14/20183/14/20183/14/2018 3:05:17 PMPPASS
Phone #: ###-#### Inspection requested via web by Randy Hart- fireplace R/I ok
MEC18-01107 Rough-in3/14/20183/14/20183/14/2018 2:46:39 PMPFAIL
Phone #: ###-#### Inspection requested via web by Randy Hart- correction on fireplace not made
MEC18-01081 Final3/14/20183/14/20183/14/2018 2:30:13 PMPPASS
Phone #: ###-#### Inspection requested via web by Melissa Skinner- final ok
MEC18-00674 Rough-in3/14/20183/14/20183/14/2018 1:43:38 PMPFAIL
Phone #: ###-#### Inspection requested via web by Krista Boss- need approved ACCA report onsite for inspection- need right address on housing before next inspection
MEC18-01030 Rough-in3/14/20183/14/20183/14/2018 11:45:10 AMAPASS
R/I ok- fireplace R/I ok
MEC18-01030 Rough-in3/14/20183/14/20183/14/2018 11:44:36 AMAPASS
fireplace R/I ok
MEC18-01137 Final3/13/20183/14/20183/14/2018 11:16:52 AMAPASS
homeowner 2083423443- Kevin 2089413166- furnace coil ac co ok
MEC17-00553 Final3/14/20183/14/20183/14/2018 11:02:23 AMAPASS
mini split ok
MEC18-01171 Rough-in3/13/20183/14/20183/14/2018 10:41:21 AMAPASS
Phone #: ###-#### Inspection requested via web by jeff jedlick- R/I ok- ok for cover
MEC18-01171 Pressure Test3/14/20183/14/20183/14/2018 10:40:37 AMAPASS
Phone #: ###-#### Inspection requested via web by jeff jedlick- 20lb gas pass
MEC18-01172 Rough-in3/13/20183/14/20183/14/2018 10:18:19 AMAFAIL
Call before going to make sure someone it there for you Phone #: ###-#### Inspection requested via web by Rene Neumeyer- appliance gas connector can not run thru appliance- need csst piping with protective sleeve or hard pipe ran to appliance
MEC18-00943 Final3/13/20183/14/20183/14/2018 9:46:04 AMAPASS
call 1/2 hr before // Mike Phone #: ###-####- 5lb flue pass- furnace ac co ok
MEC17-00553 Mec-Aging Inspection3/14/20183/14/20183/14/2018 9:26:16 AM PEND
contractor will schedule final per phone call
MEC17-05466 Final3/13/20183/14/20183/14/2018 9:17:11 AMAPASS
call clint at ###-#### for access info Inspection requested via web by Don Dowers- 20lb gas was passed and tagged on roughin- wasnt noted- Final ok
MEC18-01030 Conference3/13/20183/14/20183/14/2018 8:50:02 AMADONE
8:00 - 8:30 - RJ Phone #: ###-#### Inspection requested via web by Brandon Sorensen- went over issues with installer- talked about fireplace install b vent insulation shield nail plates and other misc stuff
MEC17-01708 Mec-Aging Inspection3/14/20183/14/20183/14/2018 8:06:32 AM DONE
MEC17-01708 Final3/14/20183/14/20183/14/2018 8:06:22 AMAPASS
should have been finaled out on first inspection
MEC17-03052 Mec-Aging Inspection3/14/20183/14/20183/14/2018 8:03:44 AM DONE
MEC17-03052 Final3/14/20183/14/20183/14/2018 8:03:32 AMAPASS
final ok- electrical permit pulled and inspected
MEC18-01137 Final3/12/20183/14/20183/13/2018 4:25:02 PMACANC
contact homeowner ###-#### or Kevin (QHC) @ Phone #: ###-#### Inspection requested via web by Kevin Pratley- fail by accident- rescheduled for tomorrow AM