Inspections for the day of: Thursday, March 14, 2019.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-00783 Final3/13/20193/14/20193/14/2019 2:18:32 PMPPASS
Call Luke on your way to meet you there ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan
Final ok
ELE17-00523 Final3/13/20193/14/20193/14/2019 2:17:41 PMPPASS
please call for access-Ren Phone #: ###-####
Shop final ok
ELE18-04646 Final3/14/20193/14/20193/14/2019 2:17:20 PMPFAIL
Please call Steve at Alloway ###-#### for lock combo Phone #: ###-#### Inspection requested via web by Steven Ragan
Work by other without permits from RADCO out of Nevada and double bonding on remote service, Contractor will assume all work. License plate #1B4C68
ELE19-00856 Final3/13/20193/14/20193/14/2019 12:49:10 PMPPASS
New circuit for A/C unit Phone #: ###-#### Inspection requested via web by Emmet Bushman
Final for A/C unit ok
ELE19-00688 Final3/14/20193/14/20193/14/2019 12:44:10 PMPPASS
Phone #: ###-#### Inspection requested via web by Barbara Szurgot
Final ok
ELE19-00747 Electrical Rough-In3/14/20193/14/20193/14/2019 12:33:26 PMPPASS
Re-inspect Units 105, 107, 108, 109. Phone #: ###-#### Inspection requested via web by Tod Lane
Units as requested ok to cover
ELE19-00571 Final3/14/20193/14/20193/14/2019 11:58:02 AMPPASS
Final for sign retro
Final ok
MIS18-00214 MIS-Aging Inspection3/14/20193/14/20193/14/2019 11:20:53 AMPPASS
All circuits were verfied and all RTU were installed under current codes and all checked out...
ELE19-00571 Electrical Rough-In3/13/20193/14/20193/14/2019 10:38:29 AMAPASS
Retrofit old lighting to new led lighting in pole sign. Requesting 9:00 am inspection time. On Site Contact is Chris @ ###-#### Phone #: ###-#### Inspection requested via web by Ken Olsen
Verified U/L listing of retro on sign
ELE19-00747 Electrical Rough-In3/13/20193/14/20193/14/2019 9:35:41 AMAFAIL
Rough in inspection of Units 105, 107, 108 and 109. Nick Prieto will be on site for questions. Phone #: ###-#### Inspection requested via web by Tod Lane
Type NM cable shall not be installed where subject to physical damage. 1 1/4 from framing member required
ELE16-03377 Final3/12/20193/14/20193/14/2019 9:08:51 AMAPASS
home is occupied Phone #: ###-#### Inspection requested via web by Darryn Coburn
Final ok