Inspections for the day of: Thursday, March 14, 2019.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-00059 Pressure Test3/14/20193/14/20193/14/2019 3:34:15 PMPPASS
field super: Daryl Thomas
DOOR CODE 6673 Phone #: ###-#### Inspection requested via web by Lisa Whitney
- 20lb gas pressure test ok for new tankless water heater done by plumber
- by the next inspection need to have permit updated with all items being worked on
gas line, 5 bathroom fans, dryer vent, water heater vent
- will also need to see a 5lb flue pressure test
MEC19-01022 Rough-in3/13/20193/14/20193/14/2019 3:02:10 PMPPART
Phone #: ###-#### Inspection requested via web by Nicholas Paige
- exhaust fan R/I on 105,107,108,109 ok
MEC19-01009 Final3/13/20193/14/20193/14/2019 2:42:27 PMPPASS
Please call Aleks on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
MEC19-01009 Pressure Test3/13/20193/14/20193/14/2019 2:42:09 PMPPASS
Please call Aleks on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- 20lb gas pressure test ok
MEC19-00205 Final3/13/20193/14/20193/14/2019 2:23:51 PMPPASS
Please call on way: Wayne ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- furnace only co ok
MEC19-00640 Rough-in3/14/20193/14/20193/14/2019 2:02:12 PMPPASS
Partial rough in. Bill Burch site contact. Phone #: ###-#### Inspection requested via web by RM Mechanical
- north system in crawl duct seal ok for insulation cover
MEC19-01011 Final3/13/20193/14/20193/14/2019 1:35:14 PMPPASS
Please call Craig on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- A/C coil co ok
MEC19-00977 Final3/12/20193/14/20193/14/2019 1:09:50 PMPPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette
- furnace ac coil co ok
MEC19-00508 Rough-in3/13/20193/14/20193/14/2019 11:48:21 AMPPASS
Please contact Bill on your way out. ###-####. Phone #: ###-#### Inspection requested via web by Vance Poulsen
- R/I ok
MEC19-00943 Final3/12/20193/14/20193/14/2019 11:44:12 AMAPASS
Field Super: Chard Robertson Phone #: ###-#### Inspection requested via web by Lisa Whitney
- furnace ac coil co ok
MEC19-00428 Final3/13/20193/14/20193/14/2019 9:30:15 AMANH
Please call Ed @ ###-#### for access to home Phone #: ###-#### Inspection requested via web by Dan Otero
- called number in notes and no answer
- no access to home left notice on front door
MEC19-00162 Rough-in3/13/20193/14/20193/14/2019 8:33:56 AMAPASS
Rough in for classrooms for duct sealing. Steve is your contact Phone #: ###-#### Inspection requested via web by Kim Adams
- duct seal on all 12" branch runs from hallway into class rooms ok and ok for insulation cover
- main trunk lines still need to be seen when finished first 15' will be lined
MEC18-02892 Mec-Aging Inspection3/14/20193/14/20193/14/2019 8:10:40 AM DONE
Called TML and talked with Debbie about their mechanical aging permit off Normandie. Permit will expire in 180 days