BLD00-03428
| FIRE-Conference | 3/13/2002 | 3/15/2002 | 3/15/2002 12:00:00 AM | A | PART |
|
|
fire for conf--calvin - ###-#### met with Jim Storey and Calvin. r/i of basement alarms; need resubmittals on larm wiring and changes 3/15/2002 11:24:18 AM
|
BLD01-00650
| FIRE-Final Inspection | 3/14/2002 | 3/15/2002 | 3/15/2002 12:00:00 AM | P | FAIL |
|
|
###-#### need additional module on alarm panel to monitor spervisory signal; horn not installed in bedroom in one unit 3/15/2002 5:11:33 PM
|
BLD01-00675
| FIRE-Final Inspection | 3/15/2002 | 3/15/2002 | 3/15/2002 12:00:00 AM | P | FAIL |
|
|
tim ###-#### electrical under hood not shutting down; need sign at manual pull designating system; system not charged by Grinnell 3/15/2002 4:13:30 PM
|
FIR02-00074
| INSP-Sprinkler Rough-in | 3/15/2002 | 3/15/2002 | 3/15/2002 12:00:00 AM | P | PART |
|
|
r/i doug ###-####- cover insp on soffets okay to cover room 103 and conference room 3/15/2002 1:48:13 PM
|
FIR02-00045
| INSP-Sprinkler Rough-in | 3/15/2002 | 3/15/2002 | 3/15/2002 12:00:00 AM | P | CANC |
|
|
doug- ###-#### r/i -cover insp on soffet Disp set to [CANC] by a contractor via Hello! on 03/15/2002 at 10:24:19.
|
FIR01-00428
| INSP-Final Inspection | 3/15/2002 | 3/15/2002 | 3/15/2002 12:00:00 AM | P | PASS |
|
|
Added by Inspector: 409 On 3/15/2002 4:14:08 PM
|