Inspections for the day of: Wednesday, March 15, 2006.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02847 ELE-Aging Inspection3/15/20063/15/20063/16/2006 12:44:28 PM PART
stopprd at site wsuc
ELE06-00872 Electrical Rough-In3/15/20063/15/20063/15/2006 4:38:36 PMPPASS
jack --re-insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok
called needs outside fixture for lighting exit contractor will install it
ELE06-00565 Final3/15/20063/15/20063/15/2006 4:11:05 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok
ELE05-03714 Rough-In Permanent Service3/15/20063/15/20063/15/2006 4:10:45 PMPCANC
Toli; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong owner needs electrical contractor to take over job he is not allowed to have permit on neww house he does not live in see J Schmer or J Frank for info
ELE05-04023 Conference3/15/20063/15/20063/15/2006 3:07:36 PMPDONE
met with testing lab tech.
ELE06-00232 Permanent Service3/15/20063/15/20063/15/2006 2:50:05 PMPPASS
dennis; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
p/s u/g new for meter suite#200 ok
ELE06-00711 Electrical Rough-In3/14/20063/15/20063/15/2006 9:33:41 AMAPART
7:00 am ispection 3 areas 1st floor anop, noted needs bond bushings where RE washers are used, needs bushings for rigid nipples, secure clips that secure raceways and cables, noted over 360 degrees of bends ceilings, basement anop all items where address while I was there