Inspections for the day of: Wednesday, March 15, 2006.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00594 INSP-Sprinkler Rough-in3/14/20063/15/20063/15/2006 6:18:20 PMAPART
Core areas including the restrooms,elevator lobby, and janitors closet on the 7th-11th floors inspected for rough-in cover, 2nd and 1st floors rough-in is good for cover, one head in the ATM room is blocked by ductwork, discussed hydro testing schedule.
FIR06-00132 INSP-Final Inspection3/14/20063/15/20063/15/2006 1:32:59 PMAPASS
Fire alarm passed field inspection.
FIR05-00710 INSP-Sprinkler Rough-in/Hydro3/14/20063/15/20063/15/2006 1:30:27 PMAPART
Overhead rough-in is good for cover at the 1st and 2nd floors only, 3rd floor inspected but not approved for cover until cold cavity protection has been installed and verified, missing nailer plate at third floor low wall main.
BLD05-01077 FIRE-Final Inspection3/14/20063/15/20063/15/2006 11:48:20 AMAFAIL
Provide keys in knox box, relocate temporary fence at alley to allow access to fire dept. WPI and FDC, provide signage at the door to the riser/pump room, provide lockout for air compressor circut switches, provide emergency egress illumination for the exit corridor from the fire command center, install work table for the fire command center.
BLD05-02310 FIRE-Final Inspection3/14/20063/15/20063/15/2006 11:44:04 AMAPASS
Fire life safety is satisfactory, inspection passed.
BLD05-02316 FIRE-Final Inspection3/14/20063/15/20063/15/2006 10:06:43 AMAFAIL
Provide suite address as indicated on review notes #4, provide means of egress illumination as indicated on review note #10, door hardware must comply with IFC 1008.1.8.1 for accessibility-see fire code review note #8. NOTE: remove the large accumulation of combustible debris adjacent to the tenant space in the vacant area immediately. The debris poses a hazard to life safety and property, and shall be removed per note #22 and requirements of IFC 1404.2.