Inspections for the day of: Thursday, March 15, 2007.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-01002 INSP-Sprinkler Rough-in/Hydro3/14/20073/15/20073/15/2007 5:57:15 PMPPART
Fire sprinkler install is good for cover at the restroom hard lids and the entryway vestibule soffits as noted on approved plans, will require as-builts reflecting all field modifications.
FIR05-00268 INSP-Final Inspection3/15/20073/15/20073/15/2007 5:52:49 PMPPASS
UG supply line permit finaled.
FIR06-00683 INSP-Final Inspection3/15/20073/15/20073/15/2007 5:51:27 PMPPASS
UG supply line permit finaled.
FIR06-00583 INSP-Sprinkler Rough-in3/15/20073/15/20073/15/2007 5:50:24 PMPPART
OH install is approved for cover at the waiting room, nurses station, north hall and as noted on city stamped plans.
FIR06-00770 INSP-Sprinkler Rough-in3/15/20073/15/20073/15/2007 1:38:44 PMPPART
Rough-in as marked on approved plans is good for cover.
FIR07-00176 INSP-Final Inspection3/8/20073/15/20073/15/2007 1:15:30 PMAPASS
Fire alarm permit work passed final field inspection.
FIR05-00402 INSP-Final Inspection3/14/20073/15/20073/15/2007 1:14:42 PMAPASS
Final fire sprinkler inspection passed, noted missing escutcheons installed while on site.
FIR06-00671 INSP-Final Inspection3/13/20073/15/20073/15/2007 11:04:32 AMAPASS
Required corrections have been field verified for compliance, final fire sprinkler inspection passed, permit finaled.
BLD06-03544 FIRE-Final Inspection3/14/20073/15/20073/15/2007 11:02:20 AMAPASS
Fire life safety finaled.
BLD06-03545 FIRE-Final Inspection3/14/20073/15/20073/15/2007 11:01:08 AMAPASS
Fire life safety inspection passed, noted two missing doors at the bathrooms to be installed prior to structural final.