Inspections for the day of: Friday, March 15, 2013.
Number of inspections: 11
Percentage of inspections complete: 91 %
Percentage of inspections not complete: 9 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00011 INSP-Sprinkler Rough-in3/11/20133/12/2013 P 
This is for the 3rd, 4th & 5th Fl. Mike B is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus
FIR11-00228 FIR-Aging Inspection3/15/20133/15/20133/21/2013 7:52:23 AM DONE
BLD13-00055 FIRE-Conference3/15/20133/15/20133/15/2013 5:10:30 PMADONE
On site meeting with Rich from Govt. buildings, T. Gainor and J. Blais regarding conditions per IFC for delayed egress. Verified new exit signs and EM lighting have been installed per previous inspection. Determined tie in to the FA system is also required unless verification of an alternate approval is provided.
BLD12-02191 FIRE-Final Inspection3/14/20133/15/20133/15/2013 4:56:51 PMPPASS
Fire life safety okayed pending max. occupant signage is posted per plan review and red-line annotations, night latch at the south exit door removed while on site.
FIR13-00008 INSP-Final Inspection3/14/20133/15/20133/15/2013 4:52:44 PMPPASS
Fire alarm testing completed and passed after adjustments made while on site. Permit finaled.
BLD13-00175 FIRE-Final Inspection3/15/20133/15/20133/15/2013 4:47:07 PMPPASS
Noted correction items completed. Fire life safety passed.
BLD13-00218 FIRE-Final Inspection3/15/20133/15/20133/15/2013 4:45:35 PMPPASS
Verified noted correction items are finished. Life safety finaled.
BLD13-00489 FIRE-Final Inspection3/14/20133/15/20133/15/2013 4:43:25 PMPPASS
Fire life safety inspection passed provided the fire extinguisher is relocated adjacent to the main exit as discussed.
FIR13-00011 INSP-Sprinkler Rough-in3/14/20133/15/20133/15/2013 4:40:26 PMAPART
Completed shell fire protection rough-in at floors 7 and 8. Noted missing hangers at floor 8, beam obstruction at the fire service elevator lobby typical per floor.
FIR13-00059 INSP-Final Inspection3/14/20133/15/20133/15/2013 4:35:29 PMAPART
Scope of work complete, functional testing passed. Final pending as-builts per red line plan review note comments.
FIR12-00038 INSP-Final Inspection3/14/20133/15/20133/15/2013 4:30:38 PMAPASS
Functional testing passed 3/14. Fire alarm permit finaled.