ELE12-02434
| ELE-Aging Inspection | 3/15/2016 | 3/15/2016 | 3/15/2016 3:44:15 PM | | PASS |
|
|
Waiting on contractor
|
ELE13-00354
| ELE-Aging Inspection | 3/15/2016 | 3/15/2016 | 3/15/2016 3:39:49 PM | | PASS |
|
|
Waiting on contractor
|
ELE12-02995
| ELE-Aging Inspection | 3/15/2016 | 3/15/2016 | 3/15/2016 3:38:54 PM | | PASS |
|
|
Waiting on owner
|
ELE16-00536
| Electrical Rough-In | 3/15/2016 | 3/15/2016 | 3/15/2016 3:38:32 PM | P | PASS |
|
|
underground; Larry Phone #: ###-#### East 1/2 of underground for parking lot rough in ok cover
|
ELE16-00822
| Rough-In Permanent Service | 3/15/2016 | 3/15/2016 | 3/15/2016 3:16:55 PM | P | PASS |
|
|
Ok for Idaho Power to turn back on Phone #: ###-#### Inspection requested via web by Randy Fletcher Service rough in ok. Water bond not complete, branch circuits not complete. Ground rods ok in window well. p/s o/h rec ok
|
ELE16-00826
| Final | 3/15/2016 | 3/15/2016 | 3/15/2016 2:46:21 PM | P | CANC |
|
|
This inspection is for a service upgrade. Please make it your last stop if possible. Daven Story is Master Elec. on site. C-###-#### Phone #: ###-#### Inspection requested via web by Brian Caruso Needed permenant service inspection.
|
ELE16-00826
| Permanent Service | 3/15/2016 | 3/15/2016 | 3/15/2016 2:45:51 PM | P | PASS |
|
|
This inspection is for a service upgrade. Please make it your last stop if possible. Daven Story is Master Elec. on site. C-###-#### Phone #: ###-#### Inspection requested via web by Brian Caruso p/s u/g rec ok
|
ELE16-00779
| Final | 3/15/2016 | 3/15/2016 | 3/15/2016 1:02:55 PM | P | PASS |
|
|
Greg is the contact his cell no is ###-#### Phone #: ###-#### Inspection requested via web by Shawna Gates Final ok
|
ELE16-00090
| Final | 3/14/2016 | 3/15/2016 | 3/15/2016 11:49:03 AM | A | PASS |
|
|
Install new pole sign. All Primary power by others. Phone #: ###-#### Inspection requested via web by Ken Olsen UL listing and disconnecting means confirmed. Final ok
|
ELE15-02908
| Final | 3/14/2016 | 3/15/2016 | 3/15/2016 11:17:08 AM | A | PASS |
|
|
We are requesting a final inspection for tomorrow 3/15/16 for the AM. Our contact is Rod @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Seal offs poured. Final ok
|
ELE16-00008
| Final | 3/15/2016 | 3/15/2016 | 3/15/2016 10:53:10 AM | A | PASS |
|
|
Rock I will see you 10 ish this morning Phone #: ###-#### Inspection requested via web by Mike Cole Final ok
|
ELE16-00819
| Rough-In Permanent Service | 3/14/2016 | 3/15/2016 | 3/15/2016 10:52:20 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ben Archibald Rough in ok cover p/s u/g n ok
|
ELE16-00536
| Electrical Rough-In | 3/15/2016 | 3/15/2016 | 3/15/2016 10:15:17 AM | P | PASS |
|
|
underground; Larry Phone #: ###-#### West side of entrance to parking lot underground rough in ok cover
|
ELE16-00765
| Rough-In Permanent Service | 3/14/2016 | 3/15/2016 | 3/15/2016 9:37:38 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by ERIC CENTERS Flex and #6 grounding electrode conductor installed for solar, need solar permit or add to existing. Receptacle outlet buried behind drywall by master shower.
|
ELE16-00800
| Electrical Rough-In | 3/14/2016 | 3/15/2016 | 3/15/2016 9:00:10 AM | A | PASS |
|
|
Inspect bond to pool rebar and equipotential grid for shockrete to pool and cover. Phone #: ###-#### Inspection requested via web by Chase Sessions Underground ok to set on grade due to back fill will create depth needed. Bonding of perimeter 4 corners, diving board stub rough in ok cover
|