Inspections for the day of: Tuesday, March 15, 2016.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD15-04239 FIRE-Final Inspection3/14/20163/15/20163/15/2016 4:01:14 PMPPART
Fire sprinkler inspection for phase 1 complete, fire alarm inspection for phase 1 complete, fire extinguishers for phase 1 in place with current inspection tags. Exit discharge illumination not installed at time of inspection, light fixtures are on order and will be installed when received. Life fire safety inspection partially complete, will be finaled after verification of exit discharge lighting install and fire apparatus access correction.
FIR15-00912 INSP-Final Inspection3/14/20163/15/20163/15/2016 2:55:09 PMPPASS
Phase 1 final fire sprinkler inspection passed/complete
FIR15-00912 INSP-Alarm Testing3/14/20163/15/20163/15/2016 2:53:50 PMPDONE
Alarm testing complete
FIR16-00074 INSP-Final Inspection3/14/20163/15/20163/15/2016 2:52:47 PMPPASS
Final fire alarm inspection for this scope of work passed/complete.
FIR15-00401 INSP-Sprinkler Rough-in/Hydro3/14/20163/15/20163/15/2016 1:39:08 PMPPASS
Underground hydrostatic (200 psi for 2 hours) test passed/complete. Main line underground flush complete.
FIR15-00396 INSP-Sprinkler Rough-in/Hydro3/14/20163/15/20163/15/2016 1:38:35 PMPPASS
Underground hydrostatic (200 psi for 2 hours) test passed/complete. Main line underground flush complete.
FIR15-00912 INSP-Sprinkler Rough-in/Hydro3/14/20163/15/20163/15/2016 11:26:03 AMAPASS
Hydrostatic test (200 psi for 2 hours) complete for the four wet systems in the fire pump room. Rough in inspection complete for phase 1 fire sprinkler piping.
BLD15-04443 FIRE-Final Inspection3/14/20163/15/20163/15/2016 10:01:49 AMAPASS
No fire sprinklers, no fire alarms, fire extinguisher is in place, tenant is going to have extinguisher inspected by licensed inspector. Life fire safety inspection passed/complete.
FIR16-00112 INSP-Final Inspection3/15/20163/15/20163/15/2016 8:57:41 AMPPASS
Final fire sprinkler inspection passed/complete
FIR16-00079 INSP-Final Inspection3/15/20163/15/20163/15/2016 8:56:50 AMAPASS
Final fire alarm inspection passed/complete
FIR15-00764 INSP-Final Inspection3/15/20163/15/20163/15/2016 8:56:16 AMAPASS
Final fire alarm inspection passed/complete