ELE18-00352
| Permanent Service | 3/15/2018 | 3/15/2018 | 3/15/2018 2:59:20 PM | P | FAIL |
|
|
Please inspect the new 400amp disconnect and meter base for permanent service. Thank you Phone #: ###-#### Inspection requested via web by Ryan Wilson 250.24(A)(4)- The grounding electrode system shall be connected where the grounded service conductor terminates in the service disconnecting means. 250.24(A)(5)- The grounded conductor shall not be connected to non-current carrying metal parts on the load side of service disconnect. 250.110- Equipment fasted in place. Non-current carrying metal parts shall be connected to an equipment grounding conductor. In meter pack sub gear
|
ELE18-00976
| Rough-In Permanent Service | 3/15/2018 | 3/15/2018 | 3/15/2018 1:49:41 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey 110.3- SER shall be secured by listed strap. Nail strap used listed for conduit only. 210.11(C)(4)- Circuit for garage receptacles shall have no other outlets. transformer. 300.4(B)(1)- Where NM cable passes thru punched or drilled holes a bushing or listed connector shall be installed to protect from physical damage. Furnace. 314.23(B)- Power bath fan hanging on wire. Secure fan in place. 352.46- A listed bushing shall be installed on service PVC riser. * What is purpose for wire hanging from ceiling by back door?
|
ELE18-00891
| Electrical Rough-In | 3/14/2018 | 3/15/2018 | 3/15/2018 10:48:37 AM | A | PASS |
|
|
The key is in the shed between the house and tiny house, it is hanging just inside the door. If you have any questions please feel free to contact Justin ###-####. Thanks!!! Phone #: ###-#### Inspection requested via web by Clayton Morgan All wiring fished in, inspection to make sure patching drywall and nail plates for shallow holes. Rough in ok cover
|
ELE18-00900
| Electrical Rough-In | 3/14/2018 | 3/15/2018 | 3/15/2018 10:07:52 AM | A | PASS |
|
|
This inspection is for the equipotential bonding plane. The gate on the right side of the apartment complex will be unlocked. If it is not here is the phone number to the manager Stan. ###-####. Phone #: ###-#### Inspection requested via web by Craig Korell Will be future inspection for luminaires and existing pool shell where rebar has been exposed and run back to equipment with underground conduits. Inspection for top 6" extension pour rebar on 4 corners stubs only rough in ok cover
|
ELE18-00027
| Final | 3/14/2018 | 3/15/2018 | 3/15/2018 9:37:14 AM | A | PASS |
|
|
David Joseph ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg Final ok
|
ELE18-00914
| Rough-In Permanent Service | 3/14/2018 | 3/15/2018 | 3/15/2018 8:46:33 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Rough in ok cover p/s u/g n ok
|