FIR19-00149
| INSP-Final Inspection | 3/15/2019 | 3/15/2019 | 3/15/2019 1:56:39 PM | P | PASS |
|
|
Final fire alarm inspection for area of work complete.
Please call ahead. Phone #: ###-#### Inspection requested via web by Gary Gambino
|
BLD18-04490
| FIRE-Final Inspection | 3/14/2019 | 3/15/2019 | 3/15/2019 1:18:42 PM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete.
Call 30 minutes ahead // Jordan Phone #: ###-####
|
BLD18-03647
| FIRE-Conference | 3/14/2019 | 3/15/2019 | 3/15/2019 12:50:16 PM | A | CANC |
|
|
Rescheduled for 18MAR2019 per conversation with point of contact. This request is cancelled.
Pre-Con meeting Phone #: ###-#### Inspection requested via web by Jimmy Martin
|
FIR19-00170
| INSP-Sprinkler Rough-in | 3/13/2019 | 3/15/2019 | 3/15/2019 12:47:32 PM | A | FAIL |
|
|
Tenting above pipe on the level 3 east end will not meet the minimum R38 requirements for tenting, piping will need to be lowered/adjusted to meet thr R38 requirements.
please call Andre Phone #: ###-#### Inspection requested via web by Chris Gregory
|
BLD18-00945
| FIRE-Final Inspection | 3/15/2019 | 3/15/2019 | 3/15/2019 12:06:50 PM | P | PART |
|
|
Fire alarm and hood suppression system inspection for kitchen area have been completed, fire extinguishers are placed with current inspection tags. Life fire safety inspection for kitchen TCO complete.
Ron-kitchen area Phone #: ###-####
|
FIR17-00612
| INSP-Final Inspection | 3/14/2019 | 3/15/2019 | 3/15/2019 12:05:19 PM | A | CANC |
|
|
Will be rescheduled to coincide with fire alarm inspection, this request is cancelled.
The contact is Jeff Chaney. He requests that he be notified ahead of time when the inspector will be there. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00244
| INSP-Final Inspection | 3/14/2019 | 3/15/2019 | 3/15/2019 12:04:39 PM | A | CANC |
|
|
Paint booth is not ready for final inspection, this request is cancelled.
Phone #: ###-#### Inspection requested via web by Eric Stanley
|
BLD18-03106
| FIRE-Final Inspection | 3/14/2019 | 3/15/2019 | 3/15/2019 12:04:02 PM | A | FAIL |
|
|
Waiting for verification of class 1 wiring and need suppression permit finaled.
Ask for Aaron or Mike at the front desk when you arrive. Phone #: ###-#### Inspection requested via web by Clayn Sonderegger
|
FIR18-00247
| INSP-Final Inspection | 3/15/2019 | 3/15/2019 | 3/15/2019 12:02:59 PM | P | PASS |
|
|
Final inspection for AES complete.
Bill Phone #: ###-####
|
BLD18-04438
| FIRE-Final Inspection | 3/14/2019 | 3/15/2019 | 3/15/2019 11:32:14 AM | A | CANC |
|
|
Duplicate inspection request, this request is cancelled.
mike Phone #: ###-####
|
FIR18-00235
| INSP-Final Inspection | 3/14/2019 | 3/15/2019 | 3/15/2019 11:17:26 AM | A | FAIL |
|
|
AES did not show NETCON 5.
Jacob Phone #: ###-####
|
BLD19-00034
| FIRE-Final Inspection | 3/14/2019 | 3/15/2019 | 3/15/2019 10:33:13 AM | A | PASS |
|
|
Final life fire safety inspection for area of work complete.
Dusty Phone #: ###-####
|
BLD18-04438
| FIRE-Final Inspection | 3/14/2019 | 3/15/2019 | 3/15/2019 10:31:11 AM | A | PART |
|
|
Partial final inspection for life fire safety complete. Glycol system and CO2 have not been installed yet, CO2 will require a detection aoarm due to amount being used. TCO for life fire safety is complete, a follow up inspection will be required after permenant CO2 system and glycol system is installed.
Duplicate inspection request, this request is cancelled.
Mike Phone #: ###-####
|
FIR19-00007
| INSP-Sprinkler Rough-in | 3/15/2019 | 3/15/2019 | 3/15/2019 10:28:09 AM | A | PASS |
|
|
All tenting in place at time of inspection, overhead fire sprinkler piping approved for cover.
Tenting inspection, call Anthony if any issues. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD17-04483
| FIRE-Final Inspection | 3/14/2019 | 3/15/2019 | 3/15/2019 10:10:38 AM | A | PASS |
|
|
Previously noted items have been corrected, final life fire safety inspection complete.
Peter Phone #: ###-####
|
BLD18-03836
| FIRE-Final Inspection | 3/13/2019 | 3/15/2019 | 3/15/2019 9:19:45 AM | A | PASS |
|
|
Fire sprinkler inspection complete (escutcheon will be installed when painting is finished) no fire sprinkler modifications, fire extinguisher are placed with current inspection tags, hood suppression system has a current inspection tag, fire sprinkler system has a current inspection tag. Final life fire safety inspection for area of work complete.
for temporary occupancy // Eric Phone #: ###-####
|
FIR19-00090
| INSP-Final Inspection | 3/15/2019 | 3/15/2019 | 3/15/2019 9:13:30 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
|
FIR18-00510
| INSP-Conference | 3/13/2019 | 3/15/2019 | 3/15/2019 8:39:52 AM | A | DONE |
|
|
Fire conference complete, Concealed combustible spaces need to meet the requirements of the 2016 NFPA 13, section 8.15.1.2
Need to talk about concealed chases and soffits can we do 8:00am? Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR18-00947
| INSP-Final Inspection | 3/14/2019 | 3/15/2019 | 3/15/2019 8:24:14 AM | A | PASS |
|
|
Final fire alarm inspection for area work compete.
Please call 1/2 hour before arriving. Thanks Phone #: ###-#### Inspection requested via web by david davis
|
FIR18-00669
| INSP-Final Inspection | 3/14/2019 | 3/15/2019 | 3/15/2019 8:23:43 AM | A | PASS |
|
|
Final fire alarm inspection for area work compete.
Please call 1/2 hour before arriving. Thanks Phone #: ###-#### Inspection requested via web by david davis
|
FIR19-00136
| INSP-Final Inspection | 3/14/2019 | 3/15/2019 | 3/15/2019 8:23:10 AM | A | PASS |
|
|
Final fire alarm inspection for area work compete.
Please call 1/2 hour before arriving. Thanks Phone #: ###-#### Inspection requested via web by david davis
|
FIR18-00951
| INSP-Final Inspection | 3/14/2019 | 3/15/2019 | 3/15/2019 8:20:30 AM | A | PASS |
|
|
Final fire alarm inspection for area work compete.
Please call 1/2 hour before arriving. Thanks Phone #: ###-#### Inspection requested via web by david davis
|
FIR18-00946
| INSP-Final Inspection | 3/12/2019 | 3/15/2019 | 3/15/2019 12:00:00 AM | A | PASS |
|
|
Please contact nate roughly 15 mins to arrival Phone #: ###-#### >> Inspection requested via web by jason petty
Verified all outstanding items were met.
|