MEC04-00666
| Rough-in | 3/12/2004 | 3/16/2004 | 3/16/2004 12:00:00 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Andrea Creek
|
MEC04-00675
| Pressure Test | 3/15/2004 | 3/16/2004 | 3/16/2004 12:00:00 AM | A | PASS |
|
|
jack; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
MEC04-00675
| Final | 3/15/2004 | 3/16/2004 | 3/16/2004 12:00:00 AM | A | FAIL |
|
|
jack; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
Insulate return air duct in crawl space and support gas line. 3/16/2004 11:10:25 AM
|
MEC03-02615
| Final | 3/16/2004 | 3/16/2004 | 3/16/2004 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 3/16/2004 at 7:03:57 AM. Contact: ###-####.
|
MEC04-00087
| Pressure Test | 3/16/2004 | 3/16/2004 | 3/16/2004 12:00:00 AM | P | FAIL |
|
|
re-inspection for pressure test for firepit and bbq in trench; Phone #: ###-#### Internet Inspection Request from: APRIL THOMAS
C/N posted on gas piping.
Need factory applied coated pipe for underground use. 10 mil tape ok at fittings only. Show that gas piping in pvc pipe is an exception for non factory coated piping. Piping through foundation wall is required to be sealed if not already done so. Need to retest gas piping. 3/16/2004 1:38:03 PM
|
BLD03-03022
| BLD-Conference | 3/16/2004 | 3/16/2004 | 3/16/2004 12:00:00 AM | P | FAIL |
|
|
frame/energy seal; Phone #: ###-#### Internet Inspection Request from: mike hill
Items 2,3,4 and 5 not completed. Not allowed to insulate. 3/16/2004 2:30:54 PM
3/16/2004 2:31:41 PM
|
BLD02-00473
| BLD-Final | 3/16/2004 | 3/16/2004 | 3/16/2004 12:00:00 AM | P | CANC |
|
|
please call 15 mins prior to inspection////###-#### shawn
Wants Tony to do inspection. 3/16/2004 2:38:53 PM
|
MEC04-00694
| Final | 3/16/2004 | 3/16/2004 | 3/16/2004 12:00:00 AM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: misty evans
Need factory coated piping for underground use. Retest gas piping. 3/16/2004 2:02:41 PM
|