ELE04-02639
| Electrical Rough-In | 3/15/2005 | 3/16/2005 | 3/16/2005 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 3/15/2005 at 8:44:25 AM. Contact: ###-####. Mainly job walk to get familiar with job, pointed out foreign piping over elect equip in elect room, signed their inspection log 3/16/2005 9:53:53 AM
|
ELE05-00655
| Final | 3/15/2005 | 3/16/2005 | 3/16/2005 12:00:00 AM | A | CANC |
|
|
cHRIS; Phone #: ###-#### Internet Inspection Request from: Jan Rice see added insp. this for r/i 3/16/2005 10:16:10 AM
|
ELE05-00777
| Final | 3/15/2005 | 3/16/2005 | 3/16/2005 12:00:00 AM | A | PASS |
|
|
reinspection on hot tub Internet Inspection Request from: Andy Rose corrections made, ok to final 3/16/2005 8:00:05 AM
|
ELE05-00332
| Final | 3/15/2005 | 3/16/2005 | 3/16/2005 12:00:00 AM | A | PASS |
|
|
calvin; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok to final 3/16/2005 8:36:14 AM
|
ELE05-00655
| Rough-In Permanent Service | 3/16/2005 | 3/16/2005 | 3/16/2005 12:00:00 AM | A | PASS |
|
|
corrections made, left survey for staple romex. ric ok, p/s u/g n ok
|
ELE05-00659
| Electrical Rough-In | 3/16/2005 | 3/16/2005 | 3/16/2005 12:00:00 AM | P | PART |
|
|
TOBY CEILING COVER; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy Clg cover ok north 1/2 and borders ok. Not front windows. Need to add show room recpts. 3/16/2005 12:36:27 PM
|
ELE05-00864
| Final | 3/15/2005 | 3/16/2005 | 3/16/2005 12:00:00 AM | P | PASS |
|
|
thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ok to final 3/16/2005 4:33:07 PM
|
ELE05-00842
| Electrical Rough-In | 3/16/2005 | 3/16/2005 | 3/16/2005 12:00:00 AM | P | FAIL |
|
|
greg; Phone #: ###-#### Internet Inspection Request from: Barbara Moore 314.23(C) rear outside light box shall be securely fastened, 334.80 ampacity of more than 2 nm cables shall be adjusted over panel,300.4(D) cable shall be 1 1/4" from edge of framing member, 314.17(A) boxes shall be replaced where openings knocked out, 210.52(A) recpt shall be installed by front door into living room,BCC all boxes shall be made up, called contr , left corr notice 3/16/2005 2:50:09 PM
|