Inspections for the day of: Thursday, March 16, 2006.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00856 FIR-Aging Inspection3/16/20063/16/20063/20/2006 2:03:25 PM NR
I spoke to Chris with SimplexGrinnell he is to follow up on status.
FIR06-00143 INSP-Sprinkler Rough-in/Hydro3/16/20063/16/20063/17/2006 11:08:12 AMPPART
Underground piping up to the 11 1/4 is ok to cover. Per contractor the piping is relocated 3' over to be under the new sidewalk and landscaping which will give it a 4'-6" bury.
FIR05-00847 INSP-Final Inspection3/15/20063/16/20063/16/2006 4:13:47 PMPFAIL
Monitoring company did not receive all of the signals and they do not have information such as address and city. Also could not do the battery calcs. Need to redo the test.
FIR05-00771 INSP-Final Inspection3/16/20063/16/20063/16/2006 4:05:59 PMPFAIL
Need pressure relief installed on the wet system and revised calcs
BLD05-02319 FIRE-Final Inspection3/15/20063/16/20063/16/2006 4:04:39 PMPCANC
no time for inspection
BLD04-03025 FIRE-Conference3/16/20063/16/20063/16/2006 4:02:37 PMPDONE
The wet stand pipes have been installed as dry temporarily with dave hannimans approval. Signage with gpm and psi requirements have been placed at the fdc. The standpipes are to be converted to wet when the building is enclosed and heated. Work can now continue on the fourth floor and above.
FIR05-00644 INSP-Sprinkler Rough-in3/15/20063/16/20063/16/2006 4:02:11 PMAPART
The wet stand pipes have been installed as dry temporarily with dave hannimans approval. Signage with gpm and psi requirements have been placed at the fdc. The standpipes are to be converted to wet when the building is enclosed and heated. Work can now continue on the fourth floor and above.
BLD04-03012 FIRE-Final Inspection3/16/20063/16/20063/16/2006 3:17:24 PMPPASS
life safety finaled
FIR05-00788 INSP-Sprinkler Rough-in3/15/20063/16/20063/16/2006 3:13:28 PMPPASS
UG inside of building is ok to cover
FIR06-00117 INSP-Sprinkler Rough-in/Hydro3/16/20063/16/20063/16/2006 1:45:32 PMPFAIL
insulation is lying on upright sprinkler heads
FIR05-00748 INSP-Final Inspection3/16/20063/16/20063/16/2006 1:44:59 PMPPASS
permit finaled
BLD00-03014 FIRE-Final Inspection3/15/20063/16/20063/16/2006 10:36:41 AMAFAIL
Wall layout does not match what is on plans.
FIR05-00693 INSP-Sprinkler Rough-in3/15/20063/16/20063/16/2006 10:15:38 AMAPASS
3" pipe rising from the first floor to the penthouse is ok to cover
BLD05-02069 FIRE-Final Inspection3/15/20063/16/20063/16/2006 9:19:37 AMAPART
A temporary occupancy was given until the fire alarm plans have been approved and inspected. Also a MIS permit will be required for the new tenant.