BLD06-02714
| FIRE-Final Inspection | 3/14/2007 | 3/16/2007 | 3/16/2007 4:27:54 PM | A | NR |
|
|
Pending project related alarm and sprinkler permit finals.
|
FIR06-00766
| INSP-Final Inspection | 3/14/2007 | 3/16/2007 | 3/16/2007 4:22:07 PM | A | DEFR |
|
|
Rescheduled due to FAB conditions.
|
FIR06-00101
| INSP-Sprinkler Rough-in/Hydro | 3/16/2007 | 3/16/2007 | 3/16/2007 4:08:59 PM | P | FAIL |
|
|
OH hydrostatic test failed for the 3" manifold system due to pressure loss at the guage, the 4" manifold system hydro passed.
|
FIR05-00883
| INSP-Sprinkler Rough-in/Hydro | 3/16/2007 | 3/16/2007 | 3/16/2007 4:05:49 PM | P | PART |
|
|
UG fire supply line hydrostatic test passed.
|
BLD06-03060
| FIRE-Final Inspection | 3/16/2007 | 3/16/2007 | 3/16/2007 3:09:05 PM | P | PASS |
|
|
Noted items at the previous inspection have been verified for completion, fire life safety finaled.
|
FIR06-00540
| INSP-Sprinkler Rough-in/Hydro | 3/15/2007 | 3/16/2007 | 3/16/2007 2:03:17 PM | A | PART |
|
|
OH hydrostatic test of the SE quadrant 5th floor (Office Max. TI) passed.
|
BLD06-03554
| FIRE-Final Inspection | 3/16/2007 | 3/16/2007 | 3/16/2007 1:50:38 PM | P | PASS |
|
|
Fire life safety inspection passed.
|
FIR07-00209
| INSP-Sprinkler Rough-in/Hydro | 3/15/2007 | 3/16/2007 | 3/16/2007 1:49:34 PM | A | FAIL |
|
|
Static pressures above 100 psi. require hangers within 1' of the end on armovers supplying pendent sprinklers at the ATM lobby.
|
FIR07-00002
| INSP-Final Inspection | 3/15/2007 | 3/16/2007 | 3/16/2007 12:15:03 PM | A | FAIL |
|
|
Horns did not function properly during alarm test.
|
BLD06-03353
| FIRE-Final Inspection | 3/16/2007 | 3/16/2007 | 3/16/2007 12:00:28 PM | A | FAIL |
|
|
Need to provide approved hardware at the second exit door as red lined on plans, a fire alarm permit will be required to connect the new duct smoke detector to the existng fire alarm control panel and remove the single strobe notification device within the TI or extend total coverage. Per S. Rogers temp. occupancy will be acceptable if door hardware is compliant and FA plans are submitted for the required changes.
|
FIR06-00721
| INSP-Final Inspection | 3/14/2007 | 3/16/2007 | 3/16/2007 11:24:47 AM | A | NR |
|
|
Inspection rescheduled.
|
FIR07-00157
| INSP-Final Inspection | 3/15/2007 | 3/16/2007 | 3/16/2007 11:22:35 AM | A | PASS |
|
|
Fire sprinkler modifications are acceptable, permit finaled.
|