Inspections for the day of: Friday, March 16, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-02714 FIRE-Final Inspection3/14/20073/16/20073/16/2007 4:27:54 PMANR
Pending project related alarm and sprinkler permit finals.
FIR06-00766 INSP-Final Inspection3/14/20073/16/20073/16/2007 4:22:07 PMADEFR
Rescheduled due to FAB conditions.
FIR06-00101 INSP-Sprinkler Rough-in/Hydro3/16/20073/16/20073/16/2007 4:08:59 PMPFAIL
OH hydrostatic test failed for the 3" manifold system due to pressure loss at the guage, the 4" manifold system hydro passed.
FIR05-00883 INSP-Sprinkler Rough-in/Hydro3/16/20073/16/20073/16/2007 4:05:49 PMPPART
UG fire supply line hydrostatic test passed.
BLD06-03060 FIRE-Final Inspection3/16/20073/16/20073/16/2007 3:09:05 PMPPASS
Noted items at the previous inspection have been verified for completion, fire life safety finaled.
FIR06-00540 INSP-Sprinkler Rough-in/Hydro3/15/20073/16/20073/16/2007 2:03:17 PMAPART
OH hydrostatic test of the SE quadrant 5th floor (Office Max. TI) passed.
BLD06-03554 FIRE-Final Inspection3/16/20073/16/20073/16/2007 1:50:38 PMPPASS
Fire life safety inspection passed.
FIR07-00209 INSP-Sprinkler Rough-in/Hydro3/15/20073/16/20073/16/2007 1:49:34 PMAFAIL
Static pressures above 100 psi. require hangers within 1' of the end on armovers supplying pendent sprinklers at the ATM lobby.
FIR07-00002 INSP-Final Inspection3/15/20073/16/20073/16/2007 12:15:03 PMAFAIL
Horns did not function properly during alarm test.
BLD06-03353 FIRE-Final Inspection3/16/20073/16/20073/16/2007 12:00:28 PMAFAIL
Need to provide approved hardware at the second exit door as red lined on plans, a fire alarm permit will be required to connect the new duct smoke detector to the existng fire alarm control panel and remove the single strobe notification device within the TI or extend total coverage. Per S. Rogers temp. occupancy will be acceptable if door hardware is compliant and FA plans are submitted for the required changes.
FIR06-00721 INSP-Final Inspection3/14/20073/16/20073/16/2007 11:24:47 AMANR
Inspection rescheduled.
FIR07-00157 INSP-Final Inspection3/15/20073/16/20073/16/2007 11:22:35 AMAPASS
Fire sprinkler modifications are acceptable, permit finaled.