ELE09-00421
| Electrical Rough-In | 3/16/2009 | 3/16/2009 | 3/16/2009 3:26:51 PM | P | PART |
|
|
Please Provide Rough-In Inspection. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean new wall food prep area
|
ELE09-00415
| Permanent Service | 3/13/2009 | 3/16/2009 | 3/16/2009 2:47:16 PM | P | FAIL |
|
|
Roger ###-#### corr. met contr note owner needs bld for occupancy with ele attached, 250.52 (A)(1) &104(A)(1) GEC within 5 ft , and bond hot and cold, 310.16 needs 3/0 cu. or 250 kc mil al for service also sun/res, 110.26(F)(1) clearence for p/s and subpanel, 230.54(B)(4) clearence from grade to p/s drop at lowest point shall be 18FT 230.24(C) srevice drop shall not be above weatherhead exception does not apply BCC and 410.62(C) if cord used for fixtures needs factory canopy or recept and cord cap,
|
ELE08-02758
| Electrical Rough-In | 3/16/2009 | 3/16/2009 | 3/16/2009 1:38:55 PM | P | FAIL |
|
|
brian Phone #: ###-#### do not cover posted owner needs to be present at time of inspection, needs conference, borken boxes, box fill outlet spacing walls and counters grding at p/s wrong, plans do not match job, have no idea if he has required circuits for kit, bath, and so on, phone number in notes was for framer,
|
ELE09-00058
| ELE-Aging Inspection | 3/16/2009 | 3/16/2009 | 3/16/2009 12:37:55 PM | | PART |
|
|
wsuc
|
ELE08-01690
| ELE-Aging Inspection | 3/16/2009 | 3/16/2009 | 3/16/2009 12:37:31 PM | | CANC |
|
|
|
ELE08-01690
| DOC - Permit Expired | 3/16/2009 | 3/16/2009 | 3/16/2009 12:37:13 PM | P | PASS |
|
|
|
ESC07-01534
| Site Final | 3/16/2009 | 3/16/2009 | 3/16/2009 11:48:04 AM | A | PASS |
|
|
ok
|
ESC08-00132
| Site Final | 3/16/2009 | 3/16/2009 | 3/16/2009 11:47:15 AM | A | PASS |
|
|
ok
|
ESC07-01151
| Site Final | 3/16/2009 | 3/16/2009 | 3/16/2009 11:46:22 AM | A | PASS |
|
|
ok
|
ESC08-00916
| General Inspection | 3/16/2009 | 3/16/2009 | 3/16/2009 10:18:06 AM | A | FAIL |
|
|
called all hard surfaces need to be cleaned
|
ELE09-00417
| Rough-In Permanent Service | 3/16/2009 | 3/16/2009 | 3/16/2009 10:16:50 AM | A | PASS |
|
|
Thank You! Phone #: ###-#### Internet Inspection Request from: Darryn Coburn r/i p/s u/g new ok
|
ESC09-00080
| General Inspection | 3/13/2009 | 3/16/2009 | 3/16/2009 9:10:58 AM | A | PASS |
|
|
RP # ###-#### hard surfaces cleaned ok
|
ELE09-00080
| Final | 3/13/2009 | 3/16/2009 | 3/16/2009 8:41:40 AM | A | CANC |
|
|
final ceiling reinspection Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA see added r/i
|
ELE09-00080
| Electrical Rough-In | 3/16/2009 | 3/16/2009 | 3/16/2009 8:41:23 AM | A | PASS |
|
|
final ceiling reinspection Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA ok
|
ESC08-01017
| General Inspection | 3/16/2009 | 3/16/2009 | 3/16/2009 8:40:47 AM | A | PASS |
|
|
ok
|