Inspections for the day of: Monday, March 16, 2009.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-04105 ELE-Aging Inspection3/16/20093/16/20093/20/2009 10:58:50 AM PASS
ok
ELE07-04183 ELE-Aging Inspection3/16/20093/16/20093/17/2009 4:00:32 PM PASS
ELE08-02223 ELE-Aging Inspection3/16/20093/16/20093/16/2009 4:02:26 PM PASS
ELE08-02223 DOC - Permit Finaled3/16/20093/16/20093/16/2009 4:02:13 PMPPASS
ELE09-00418 Electrical Rough-In3/16/20093/16/20093/16/2009 3:26:00 PMPPART
Shawn Phone #: ###-####
walls and hard lids ok
ELE09-00095 Final3/16/20093/16/20093/16/2009 2:56:26 PMPPASS
please give me a call half an hour before inspection so that I can insure someone is home to let you in. Thanks Shaun ###-#### Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman
no esc in project
ELE08-03051 Electrical Rough-In3/16/20093/16/20093/16/2009 12:57:07 PMPPASS
justin Phone #: ###-####
floor heat ok
ELE09-00388 Permanent Service3/16/20093/16/20093/16/2009 11:40:13 AMPFAIL
william Phone #: ###-####
remove mc sheath from GEC. drive groundrods flush install plastic romex connector on GEC. #6 neutral to be white for entire length recep to be 6 ft from hot tub.
ESC08-00986 General Inspection3/16/20093/16/20093/16/2009 10:25:36 AMAPASS
looks ok
ELE09-00031 Final3/13/20093/16/20093/16/2009 10:25:11 AMAPASS
Please call Heath @###-#### prior to arrival to ensure access. Phone #: ###-#### Internet Inspection Request from: Joe Thomas
ELE09-00405 Electrical Rough-In3/13/20093/16/20093/16/2009 9:43:35 AMAPASS
Larry Phone #: ###-####
no access
R/I Ok