Inspections for the day of: Monday, March 16, 2009.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy James
TitleMEC-COM/RES INSPECTOR
Phone #794-9461
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC09-00144 Rough-in3/16/20093/16/20093/17/2009 4:32:33 PMPFAIL
Compete rough. Area B
Bill Hunt ###-#### Internet Inspection Request from: Jason King
scheduled conf for thursday with jim and alan to talk about combustion air shaft
MEC09-00525 Final3/13/20093/16/20093/16/2009 3:15:39 PMPFAIL
Please inspect as close to 4:00pm as possible. Call with any problems. Thanks, April.
Phone #: ###-#### Internet Inspection Request from: April Sims
all hydronic piping required to be completed before final can be completed, need metal strap for support to flue and air intake, see manual for correct flue and intake termination to exterior, pressure relief valves and condensate drain are not completed at this time
MEC09-00525 Pressure Test3/13/20093/16/20093/16/2009 3:08:32 PMPPASS
Please inspect as close to 4:00pm as possible. Call with any problems. Thanks, April.
Phone #: ###-#### Internet Inspection Request from: April Sims
20# test
MEC09-00553 Pressure Test3/16/20093/16/20093/16/2009 2:52:46 PMPPASS
anthony Phone #: ###-####
MEC09-00553 Final3/16/20093/16/20093/16/2009 2:52:37 PMPPASS
anthony Phone #: ###-####
MEC09-00532 Final3/16/20093/16/20093/16/2009 2:33:53 PMPPASS
Reinspect: please call Derek for access.
###-#### Thank You! Internet Inspection Request from: Ina Schneider
MEC09-00532 Pressure Test3/16/20093/16/20093/16/2009 2:33:45 PMPPASS
Reinspect: please call Derek for access.
###-#### Thank You! Internet Inspection Request from: Ina Schneider
60# test
MEC08-01714 Final3/16/20093/16/20093/16/2009 2:05:18 PMPFAIL
Final inspection. House should be open thanks Phone #: ###-#### Internet Inspection Request from: Lisa Whitney
need sediment trap before gas regulator and test port after regulator
MEC08-01072 Rough-in3/13/20093/16/20093/16/2009 11:47:53 AMAPASS
please Ron Bolen Phone #: ###-#### Internet Inspection Request from: AMANDA FARNSWORTH
ok grease duct wrap, water heaters, fume hoods, cafeteria, library, ok to insulate ducts in locker rooms
MEC09-00530 Final3/12/20093/16/20093/16/2009 11:44:15 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Elisa Worrell
ESC06-01192 Aging Inspection3/16/20093/16/20093/16/2009 10:16:09 AM CANC
ESC06-01192 DOC - Permit Expired3/16/20093/16/20093/16/2009 10:15:56 AMAPASS
MEC09-00213 Rough-in3/13/20093/16/20093/16/2009 10:15:09 AMAPASS
cover inspection - brandon Phone #: ###-#### Internet Inspection Request from: Brandon Sorensen
ok to cover core restrooms
MEC08-01221 MEC-Aging Inspection3/16/20093/16/20093/16/2009 9:41:33 AM CANC
MEC09-00242 Final3/13/20093/16/20093/16/2009 9:35:10 AMAFAIL
Tena Phone #: ###-####
need approved ul 181 tape to dryer duct and bath fans, bath fans duct required to have screws, dryer duct required to terminate 3' away from window, need b-vent to extend 6" away from wall, need to verify combustion air to space, owner needs to decide if she is putting a door to laundry room
MEC09-00536 Conference3/13/20093/16/20093/16/2009 9:32:01 AMACANC
Phone #: ###-#### Internet Inspection Request from: Yolanda Morris
MEC09-00536 Final3/16/20093/16/20093/16/2009 9:18:56 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Yolanda Morris
90 degree elbow to air intake on furnace and need primer used to pvc flue