Inspections for the day of: Friday, March 16, 2012.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-00535 Permanent Service3/15/20123/16/20123/16/2012 2:40:19 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Clint Tate p/s o/h rec ok, will call for final after power transfer and inside equipment moved
ELE11-01327 ELE-Aging Inspection3/16/20123/16/20123/16/2012 2:28:43 PM DONE
see final
ELE11-01327 Final3/16/20123/16/20123/16/2012 2:28:28 PMPPASS
ok final
ELE12-00558 Final3/16/20123/16/20123/16/2012 2:27:20 PMPFAIL
bill Phone #: ###-#### >> Inspection requested via web by William Hadzor called, told contractor to call for p/s, BCC shall bring service up to 2008 code, no violations shall be retained, shall go to job to see violations, shall not allow service conductors to be abrading roof surface, shall provide grounding, work space, etc
ELE12-00555 Electrical Rough-In3/15/20123/16/20123/16/2012 1:42:05 PMPPASS
Ready for rough-in inspection. Call my office @ ###-#### for the lock-box code for access. I will most likely be onsite however. Thanks, Dan. cell ###-####. Phone #: ###-#### >> Inspection requested via web by Dan Mitchell ri ok
ELE12-00542 Permanent Service3/15/20123/16/20123/16/2012 12:43:09 PMPPASS
Paul Phone #: ###-#### >> Inspection requested via web by Sean DeLacy p/s u/g rec ok
ELE12-00390 Final3/15/20123/16/20123/16/2012 10:22:21 AMAPASS
ryan Phone #: ###-#### ok final
ELE11-02772 Electrical Rough-In3/15/20123/16/20123/16/2012 10:04:03 AMAPASS
Floor heat inspection + 3 bathrooms Phone #: ###-#### >> Inspection requested via web by John VanZandt ok cover floor heat
ELE12-00554 Final3/15/20123/16/20123/16/2012 9:34:23 AMAFAIL
- (2) new 50A pedestals (space 41&43)
- (1) new 100A main panel (space 41)
- (1) new 100A overhead feed from existing meter main in space 37 Phone #: ###-#### >> Inspection requested via web by Lars Johnson called, shall call for p/s, NEC 300.5 top of conduit shall be 18" below surface, 110.26 shall provide free and clear work space in front of panel, 250.56 shall provide 2 ground rods at each service, 110.22 shall label disconnects
ELE12-00467 Electrical Rough-In3/15/20123/16/20123/16/2012 9:09:34 AMACANC
mark Phone #: ###-#### see conference
ELE12-00467 Conference3/16/20123/16/20123/16/2012 9:09:22 AMADONE
mark Phone #: ###-#### same comments as nr on 3-15-12
ELE12-00193 Electrical Rough-In3/15/20123/16/20123/16/2012 8:16:32 AMAPASS
Grid Ceiling Cover Inspection Please. Call Lynn Proctor at ###-#### with any questions. Phone #: ###-#### >> Inspection requested via web by Lynn Proctor ok cover ceiling