ELE12-00535
| Permanent Service | 3/15/2012 | 3/16/2012 | 3/16/2012 2:40:19 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Clint Tate p/s o/h rec ok, will call for final after power transfer and inside equipment moved
|
ELE11-01327
| ELE-Aging Inspection | 3/16/2012 | 3/16/2012 | 3/16/2012 2:28:43 PM | | DONE |
|
|
see final
|
ELE11-01327
| Final | 3/16/2012 | 3/16/2012 | 3/16/2012 2:28:28 PM | P | PASS |
|
|
ok final
|
ELE12-00558
| Final | 3/16/2012 | 3/16/2012 | 3/16/2012 2:27:20 PM | P | FAIL |
|
|
bill Phone #: ###-#### >> Inspection requested via web by William Hadzor called, told contractor to call for p/s, BCC shall bring service up to 2008 code, no violations shall be retained, shall go to job to see violations, shall not allow service conductors to be abrading roof surface, shall provide grounding, work space, etc
|
ELE12-00555
| Electrical Rough-In | 3/15/2012 | 3/16/2012 | 3/16/2012 1:42:05 PM | P | PASS |
|
|
Ready for rough-in inspection. Call my office @ ###-#### for the lock-box code for access. I will most likely be onsite however. Thanks, Dan. cell ###-####. Phone #: ###-#### >> Inspection requested via web by Dan Mitchell ri ok
|
ELE12-00542
| Permanent Service | 3/15/2012 | 3/16/2012 | 3/16/2012 12:43:09 PM | P | PASS |
|
|
Paul Phone #: ###-#### >> Inspection requested via web by Sean DeLacy p/s u/g rec ok
|
ELE12-00390
| Final | 3/15/2012 | 3/16/2012 | 3/16/2012 10:22:21 AM | A | PASS |
|
|
ryan Phone #: ###-#### ok final
|
ELE11-02772
| Electrical Rough-In | 3/15/2012 | 3/16/2012 | 3/16/2012 10:04:03 AM | A | PASS |
|
|
Floor heat inspection + 3 bathrooms Phone #: ###-#### >> Inspection requested via web by John VanZandt ok cover floor heat
|
ELE12-00554
| Final | 3/15/2012 | 3/16/2012 | 3/16/2012 9:34:23 AM | A | FAIL |
|
|
- (2) new 50A pedestals (space 41&43) - (1) new 100A main panel (space 41) - (1) new 100A overhead feed from existing meter main in space 37 Phone #: ###-#### >> Inspection requested via web by Lars Johnson called, shall call for p/s, NEC 300.5 top of conduit shall be 18" below surface, 110.26 shall provide free and clear work space in front of panel, 250.56 shall provide 2 ground rods at each service, 110.22 shall label disconnects
|
ELE12-00467
| Electrical Rough-In | 3/15/2012 | 3/16/2012 | 3/16/2012 9:09:34 AM | A | CANC |
|
|
mark Phone #: ###-#### see conference
|
ELE12-00467
| Conference | 3/16/2012 | 3/16/2012 | 3/16/2012 9:09:22 AM | A | DONE |
|
|
mark Phone #: ###-#### same comments as nr on 3-15-12
|
ELE12-00193
| Electrical Rough-In | 3/15/2012 | 3/16/2012 | 3/16/2012 8:16:32 AM | A | PASS |
|
|
Grid Ceiling Cover Inspection Please. Call Lynn Proctor at ###-#### with any questions. Phone #: ###-#### >> Inspection requested via web by Lynn Proctor ok cover ceiling
|