FIR14-00623
| INSP-Sprinkler Rough-in | 3/16/2015 | 3/16/2015 | 3/17/2015 9:49:11 AM | P | PASS |
|
|
Rough-in passed. Piping can not be covered untill tenting has been passed
|
NAF15-00003
| INSP-Final | 3/13/2015 | 3/16/2015 | 3/16/2015 2:52:35 PM | A | FAIL |
|
|
All of the canopies were missing from the sprinkler pendants and the shipping caps are still installed
|
BLD14-02689
| FIRE-Final Inspection | 3/16/2015 | 3/16/2015 | 3/16/2015 2:45:43 PM | P | FAIL |
|
|
Replace ceiling tile, provide fire extinguisher, provide emergency lighting
|
BLD15-00738
| FIRE-Final Inspection | 3/13/2015 | 3/16/2015 | 3/16/2015 1:42:50 PM | A | PART |
|
|
A temporary occupancy is being given with Scotts permission. The fire extinguishe will be tagged and mounted by Don at ###-#### this afternoon and he will also repair the non-required exit sign and emergency lights. Per Emily in addressing the Suite B is ok to remain.
|
BLD14-01652
| FIRE-Final Inspection | 3/16/2015 | 3/16/2015 | 3/16/2015 12:18:13 PM | P | FAIL |
|
|
Provide small documents, provide address, provide fire extinguishers
|
FIR15-00105
| INSP-Sprinkler Rough-in/Hydro | 3/13/2015 | 3/16/2015 | 3/16/2015 12:15:51 PM | A | PASS |
|
|
Overhead hydro of the wet system passed. Fire pump assembly not hydro tested. Rough-in of the fire pump assembly passed.
|
FIR14-00617
| INSP-Sprinkler Rough-in | 3/13/2015 | 3/16/2015 | 3/16/2015 12:14:06 PM | A | PASS |
|
|
Tenting passed. Piping is ok to cover
|
BLD15-00438
| FIRE-Final Inspection | 3/13/2015 | 3/16/2015 | 3/16/2015 9:48:31 AM | A | FAIL |
|
|
Still need the fire alarm control panel repaired. It appears that a permit has been submitted for a wireless dialer. Also one exit sign/emergency light failed by Room 119
|