Inspections for the day of: Wednesday, March 16, 2016.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-01033 ELE-Aging Inspection3/16/20163/16/20163/17/2016 11:39:35 AM CANC
too busy
ELE11-02792 ELE-Aging Inspection3/16/20163/16/20163/17/2016 11:39:03 AM CANC
too busy
ELE15-03869 Electrical Rough-In3/15/20163/16/20163/16/2016 2:48:00 PMPCANC
Mitchell Phone #: ###-#### home owner not ready
ELE16-00425 Electrical Rough-In3/15/20163/16/20163/16/2016 2:39:28 PMPFAIL




















Kitchen cover, please call when headed my way. ###-####. Thanks Richard


Phone #: ###-#### Inspection requested via web by Richard Corn wire nut for range splice not rated for copper@all. 334 type NM cable shall not be installed where subject to physical damage(wire ran behind drawers behind shelf for pensila outlet) walls ok cover
ELE15-03321 Electrical Rough-In3/15/20163/16/20163/16/2016 2:13:35 PMPFAIL
ceiling inspection Phone #: ###-#### Inspection requested via web by Bryan Atkins 400.8 flexible cords shall not be installed above drop cielings(rite of F/P) all other areas ok cover
ELE16-00808 Rough-In Permanent Service3/16/20163/16/20163/16/2016 1:21:57 PMPPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn rough-in ok cover p/s u/g n ok
ELE16-00849 Temporary Service3/16/20163/16/20163/16/2016 11:51:54 AMPCANC
Temp power pole Phone #: ###-#### Inspection requested via web by Chris Chesnut needed another day
ELE16-00146 Final3/15/20163/16/20163/16/2016 10:43:26 AMAPART
Ready for final space will be open Phone #: ###-#### Inspection requested via web by Kevin Oderkirk partial only need to verify office furnishing
ELE16-00454 Permanent Service3/15/20163/16/20163/16/2016 10:13:32 AMAPASS
Phone #: ###-#### Inspection requested via web by Don Conley p/s o/h n ok
ELE16-00835 Final3/15/20163/16/20163/16/2016 9:31:28 AMAFAIL
Brandon Greeson is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce 110.24 available arc fault calculation required prior to being energized 110.16 arc flash sticker required
ELE15-04113 Electrical Rough-In3/16/20163/16/20163/16/2016 9:15:24 AMAPASS
Bath floor heat Phone #: ###-#### Inspection requested via web by John VanZandt back bathrooms floor heat ok cover
ELE15-03661 Electrical Rough-In3/16/20163/16/20163/16/2016 8:40:00 AMAPASS
please call prior to inspection Phone #: ###-#### Inspection requested via web by BARRY KENDALL back office walls only ok cover
ELE16-00832 Electrical Rough-In3/15/20163/16/20163/16/2016 8:04:38 AMAPASS
Need inspection to cover trench between house and garage. Inspection requested via web by Alan Lusk underground from detached garage to house ok cover
ELE16-00633 Permanent Service3/15/20163/16/20163/15/2016 1:48:27 PMAPASS
Permanent service inspection was performed on Monday 14th with the rough in but the inspection requested was for rough-in. Idaho Power will need the permanent service inspection in the PDS system. Thank you. Phone #: ###-#### Inspection requested via web by David Mackey p/s u/g n ok