Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-00895 Final3/13/20203/16/20203/16/2020 3:01:05 PMPPASS
Please inspect early PM and call Aric on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks...converted existing 240v circuit to 120v...breaker blanks installed...receptacle operational...ok to final
ELE20-00645 Final3/16/20203/16/20203/16/2020 2:54:38 PMPFAIL
bILL Phone #: ###-####...
TCO ok for new areas and breakroom
FAIL...
1) hard wired appliance shall have disconnect within sight...new water heater
2) new minisplit circuit not rated for nameplate rating...MOCP and MCA not met
3) all disconnects shall be labelled with panel location and branch circuit ..mini split
4) panel circuits shall be labelled with their clear and specific purpose
ELE19-03280 Electrical Rough-In3/13/20203/16/20203/16/2020 1:39:54 PMPPASS
Cole Phone #: ###-####...rough in of shop area ok...prefabed and insulated wall
ELE19-03280 Permanent Service3/16/20203/16/20203/16/2020 1:38:59 PMPPASS
Cole Phone #: ###-####...
p/s o/h reconnect ok
ELE19-04872 Final3/13/20203/16/20203/16/2020 12:28:03 PMAPASS
Phone #: ###-#### Inspection requested via web by Barbara Szurgot...ok to final
ELE19-04898 Electrical Rough-In3/13/20203/16/20203/16/2020 10:00:09 AMAPASS
Electrical Rough-in for solar. Phone #: ###-#### Inspection requested via web by Bryan Lawley...UL listings verified...adding to existing system...all accessible
ELE20-00829 Rough-In Permanent Service3/13/20203/16/20203/16/2020 9:32:06 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn...
rough in ok to cover
p/s u/g new ok
ELE20-00198 Final3/13/20203/16/20203/16/2020 8:45:55 AMAPASS
Garage code 2468 Phone #: ###-#### Inspection requested via web by Darryn Coburn..ok to final
ELE20-00067 Final3/11/20203/16/20203/12/2020 8:19:33 AMPCANC
Call Treon 208 972 2383 Phone #: ###-#### >> Inspection requested via web by Scott Campbell Inspection cancelled from web by: Scott Campbell