ELE20-00895
| Final | 3/13/2020 | 3/16/2020 | 3/16/2020 3:01:05 PM | P | PASS |
|
|
Please inspect early PM and call Aric on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks...converted existing 240v circuit to 120v...breaker blanks installed...receptacle operational...ok to final
|
ELE20-00645
| Final | 3/16/2020 | 3/16/2020 | 3/16/2020 2:54:38 PM | P | FAIL |
|
|
bILL Phone #: ###-####... TCO ok for new areas and breakroom FAIL... 1) hard wired appliance shall have disconnect within sight...new water heater 2) new minisplit circuit not rated for nameplate rating...MOCP and MCA not met 3) all disconnects shall be labelled with panel location and branch circuit ..mini split 4) panel circuits shall be labelled with their clear and specific purpose
|
ELE19-03280
| Electrical Rough-In | 3/13/2020 | 3/16/2020 | 3/16/2020 1:39:54 PM | P | PASS |
|
|
Cole Phone #: ###-####...rough in of shop area ok...prefabed and insulated wall
|
ELE19-03280
| Permanent Service | 3/16/2020 | 3/16/2020 | 3/16/2020 1:38:59 PM | P | PASS |
|
|
Cole Phone #: ###-####... p/s o/h reconnect ok
|
ELE19-04872
| Final | 3/13/2020 | 3/16/2020 | 3/16/2020 12:28:03 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot...ok to final
|
ELE19-04898
| Electrical Rough-In | 3/13/2020 | 3/16/2020 | 3/16/2020 10:00:09 AM | A | PASS |
|
|
Electrical Rough-in for solar. Phone #: ###-#### Inspection requested via web by Bryan Lawley...UL listings verified...adding to existing system...all accessible
|
ELE20-00829
| Rough-In Permanent Service | 3/13/2020 | 3/16/2020 | 3/16/2020 9:32:06 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn... rough in ok to cover p/s u/g new ok
|
ELE20-00198
| Final | 3/13/2020 | 3/16/2020 | 3/16/2020 8:45:55 AM | A | PASS |
|
|
Garage code 2468 Phone #: ###-#### Inspection requested via web by Darryn Coburn..ok to final
|
ELE20-00067
| Final | 3/11/2020 | 3/16/2020 | 3/12/2020 8:19:33 AM | P | CANC |
|
|
Call Treon 208 972 2383 Phone #: ###-#### >> Inspection requested via web by Scott Campbell Inspection cancelled from web by: Scott Campbell
|