BLD02-01533
| FIRE-Final Inspection | 3/14/2003 | 3/17/2003 | 3/17/2003 12:00:00 AM | A | FAIL |
|
|
###-#### need sfd infilled per plans; need alternate floor elevator recall; monitor all tampers; sprinkler all areas; interconnect all standpipes 3/17/2003 10:44:34 AM
|
BLD02-01413
| FIRE-Final Inspection | 3/14/2003 | 3/17/2003 | 3/17/2003 12:00:00 AM | A | FAIL |
|
|
###-#### ###-#### need alternate floor elevator recall; monitor all tampers; sprinkler all areas; interconnect all standpipes; install alarm notification in all walkways and lobbies; need alarm notification on second floor open office area; 3/17/2003 10:45:49 AM
|
BLD00-02893
| FIRE-Final Inspection | 3/14/2003 | 3/17/2003 | 3/17/2003 12:00:00 AM | A | PASS |
|
|
glen; Phone #: ###-#### x2227 Internet Inspection Request from: Annette Moore okay per plans; no card to sign off; told Lynn to call for structural final 3/17/2003 9:44:05 AM
|
FIR03-00060
| INSP-Sprinkler Rough-in/Hydro | 3/17/2003 | 3/17/2003 | 3/17/2003 12:00:00 AM | P | FAIL |
|
|
john; Phone #: ###-#### Internet Inspection Request from: Annette Moore need 1 inch meter as 3/4 inch is installed; need Ames BFP as Watts is installed; need domestic shut off before sprinkler controls; need to move heads one foot away from ceiling heat vents; 3/17/2003 3:27:31 PM
|