FIR03-00086
| INSP-Final Inspection | 3/14/2003 | 3/17/2003 | 3/17/2003 12:00:00 AM | A | FAIL |
|
|
Test south duct detector, Provide 60 hour battery backup per review note #7. The actual standby current draw is 400Ma which requires 28.8 AH batteries. Existing duct detector zone is labeled tamper/supervisory, relabel for the devices, provide map per review note #4, mount smoke detector on deck, provide dedicated circuit per review note #11 and as stated on the plans, verify signals 3/17/2003 11:16:10 AM
|
BLD02-02756
| FIRE-Final Inspection | 3/17/2003 | 3/17/2003 | 3/17/2003 12:00:00 AM | P | PASS |
|
|
Fire life/safety finaled 3/17/2003 3:53:06 PM 3/17/2003 3:53:38 PM
|