Inspections for the day of: Monday, March 17, 2003.
Number of inspections: 2
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00086 INSP-Final Inspection3/14/20033/17/20033/17/2003 12:00:00 AMAFAIL
Test south duct detector, Provide 60 hour battery backup per review note #7. The actual standby current draw is 400Ma which requires 28.8 AH batteries. Existing duct detector zone is labeled tamper/supervisory, relabel for the devices, provide map per review note #4, mount smoke detector on deck, provide dedicated circuit per review note #11 and as stated on the plans, verify signals 3/17/2003 11:16:10 AM
BLD02-02756 FIRE-Final Inspection3/17/20033/17/20033/17/2003 12:00:00 AMPPASS
Fire life/safety finaled 3/17/2003 3:53:06 PM 3/17/2003 3:53:38 PM