Inspections for the day of: Friday, March 17, 2006.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-03668 ELE-Aging Inspection3/17/20063/17/20063/20/2006 11:46:51 AM PART
called waiting for info from contractor
ELE05-03958 ELE-Aging Inspection3/17/20063/17/20063/17/2006 4:19:21 PM PART
called cotractor he will follow up and schedule final inspection when ready
ELE05-04023 Final3/17/20063/17/20063/17/2006 4:13:08 PMPPASS
Scheduled by a contractor via Hello! on 3/17/2006 at 9:04:28 AM. Contact: ###-####. contractor made correction,surfsce extension from jbox entela testing field evaluation ok all equipment passed and labeled, card signed
ELE06-00863 Temporary Service3/17/20063/17/20063/17/2006 3:37:20 PMPPASS
Rhonda ###-####; reinspect because changed from underground to overhead per Idaho Power requirements; okay for reinspection per Jack Frank as stated by Rhonda (Falcon Electric)
t/s o/h new ok jf changed from u/g to o/h
ELE06-00881 Rough-In Permanent Service3/17/20063/17/20063/17/2006 3:13:47 PMPPASS
house is locked you need to call ###-#### 30 min. prior for access; Phone #: ###-#### Internet Inspection Request from: joe wheeler corrections made permit updated to 5 rms r/i ok p/s o/h rec. ok
ELE05-04417 Electrical Rough-In3/17/20063/17/20063/17/2006 2:25:27 PMPPART
Scheduled by a contractor via Hello! on 3/17/2006 at 7:15:24 AM. u/g for pole lights and PIV valve front and back lots
ELE05-04151 Final3/17/20063/17/20063/17/2006 1:40:29 PMPPASS
Rick; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ok
ELE05-03886 Final3/16/20063/17/20063/17/2006 12:57:37 PMACANC
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs see added conf.
ELE05-03886 Conference3/17/20063/17/20063/17/2006 12:57:08 PMPDONE
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs met with Bob R and contractor we disccussed the violations Bob posted and contractor did not correct
ELE05-04071 Conference3/17/20063/17/20063/17/2006 12:09:34 PMADONE
per jack for conf ok
ELE06-00586 Final3/10/20063/17/20063/17/2006 10:46:02 AMANH
We wired a new 30 amp 3 wire circuit to a new box below the panel. The home owner is installing his own receptacle om this circuit.Thanks!!! Dan.; Phone #: notice posted called
ELE06-00858 Final3/16/20063/17/20063/17/2006 10:03:05 AMAPASS
CALL MILES TO MEET @ ###-####. INSPECT HOT TUB . THANK YOU.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH
ELE06-00738 Final3/16/20063/17/20063/17/2006 9:20:01 AMAPASS
NEED FINAL ON FURNACE INSTALL.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ok
ELE06-00881 Rough-In Permanent Service3/16/20063/17/20063/17/2006 8:49:43 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: joe wheeler corr. do not cover, and fee due posted needs to update permit to 5 rooms called 300.4 (A)(1)(D) nail plates and 11/4" everywhere, 110.3(A&B) GEC shall terminate into one terminal only at p/s, 210.52(A,B,C) nedds outlet wall new wall space kit, also countertop spacing over 4ft between recepts, 250.24(A)(1) all water grds and bonds shall terminate at service not subpanel bond hot and cold where is it?