FIR06-00025
| INSP-Final Inspection | 3/16/2006 | 3/17/2006 | 3/24/2006 3:00:05 PM | P | DEFR |
|
|
To be rescheduled.
|
FIR05-00594
| INSP-Sprinkler Rough-in | 3/16/2006 | 3/17/2006 | 3/17/2006 3:41:49 PM | P | PART |
|
|
Third and fourth floor overhead rough-in is acceptable for cover.
|
FIR06-00154
| INSP-Final Inspection | 3/16/2006 | 3/17/2006 | 3/17/2006 2:55:12 PM | A | PART |
|
|
Hood suppression system functioned properly under test conditions, flame separation between fryer and range is not yet provided, need to install K class extinguisher.
|
FIR06-00038
| INSP-Final Inspection | 3/16/2006 | 3/17/2006 | 3/17/2006 2:34:44 PM | A | FAIL |
|
|
Various locations are overspaced beyond the maximum design area/density of 148 ft2, overspaced locations are marked on approved plans, one room marked as "file room" shall be spaced for ordinary hazard.
|
FIR05-00575
| INSP-Alarm Testing | 3/16/2006 | 3/17/2006 | 3/17/2006 1:34:51 PM | A | PART |
|
|
Per state elevator requirements, the top of shaft will require a heat detector, need to test elevator lobby SD 3rd floor north and smoke and heat in top of shaft, outside bell repaired while on site, panel, sprinkler, notification, alarm, supervision, trouble and EOL tested okay, provide signal verification as discussed, provide as-builts and updated map at next inspection, provide signage at the door to the FACP.
|
FIR05-00273
| INSP-Final Inspection | 3/16/2006 | 3/17/2006 | 3/17/2006 1:24:59 PM | A | PART |
|
|
Items on previous correction notice have been completed, per state elevator requirements the wood framed sheetrocked shaft is considered combustible and will require a sprinkler at the top.
|
BLD04-00944
| FIRE-Final Inspection | 3/16/2006 | 3/17/2006 | 3/17/2006 1:11:23 PM | A | FAIL |
|
|
Fire extinguishers are not installed, curb painting is not complete, door hardware in some locations is not installed, fire alarm and sprinkler permits must be finaled prior to life safety final, project life safety not ready for inspection at this time.
|
FIR05-00888
| INSP-Final Inspection | 3/15/2006 | 3/17/2006 | 3/17/2006 12:59:45 PM | A | PART |
|
|
Fire alarm work tested satisfactory, final pending completion of the related shell alarm permit.
|
FIR05-00889
| INSP-Final Inspection | 3/15/2006 | 3/17/2006 | 3/17/2006 12:58:32 PM | A | FAIL |
|
|
Insufficient visual coverage at the "work area" as indicated on plans, duct detector and pull stations tested okay.
|
BLD05-03176
| FIRE-Final Inspection | 3/16/2006 | 3/17/2006 | 3/17/2006 11:24:43 AM | A | PART |
|
|
Temporary occupancy approval pending building structural inspection. Fire final pending verification of fire sprinkler plan resubmittals.
|
FIR06-00037
| INSP-Final Inspection | 3/16/2006 | 3/17/2006 | 3/17/2006 10:15:46 AM | A | PART |
|
|
Verified forward flow, PIV tamper has been disconnected from outside water flow bell as discussed, final pending plan resubmittals as required.
|