BLD05-02158
| FIRE-Final Inspection | 3/11/2008 | 3/12/2008 | | A | |
|
|
|
FIR07-00425
| INSP-Final Inspection | 3/17/2008 | 3/17/2008 | 3/17/2008 4:08:48 PM | A | FAIL |
|
|
See correction notice on site for a list of defficient items including missing escutcheons, one overspaced head, painted heads, travel caps needing removal, tape and paper at some heads, etc.
|
FIR08-00192
| INSP-Final Inspection | 3/17/2008 | 3/17/2008 | 3/17/2008 4:04:36 PM | P | PASS |
|
|
Corrections are acceptable, fire sprinkler permit finaled.
|
FIR07-00937
| INSP-Sprinkler Rough-in/Hydro | 3/17/2008 | 3/17/2008 | 3/17/2008 4:03:59 PM | P | PART |
|
|
UG fire supply line hydrostatic test completed satisfactory.
|
FIR08-00073
| INSP-Conference | 3/17/2008 | 3/17/2008 | 3/17/2008 4:02:53 PM | P | DONE |
|
|
On site visit regarding duct detector locations.
|
FIR07-00937
| INSP-Supply line flush | 3/17/2008 | 3/17/2008 | 3/17/2008 2:04:23 PM | P | PART |
|
|
UG fire supply line flush completed in conjunction with United Water company.
|
FIR08-00187
| INSP-Final Inspection | 3/17/2008 | 3/17/2008 | 3/17/2008 2:02:44 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR08-00187
| INSP-Sprinkler Rough-in/Hydro | 3/17/2008 | 3/17/2008 | 3/17/2008 2:02:12 PM | P | PART |
|
|
Tenant fire sprinkler modifications are okay for cover.
|
FIR08-00170
| INSP-Final Inspection | 3/17/2008 | 3/17/2008 | 3/17/2008 1:57:32 PM | P | FAIL |
|
|
SW heads at two elevator pit locations are overspaced per head listing.
|
FIR08-00121
| INSP-Alarm Testing | 3/17/2008 | 3/17/2008 | 3/17/2008 1:55:58 PM | A | FAIL |
|
|
See on site correction notice regarding off site monitoring requirements.
|
BLD06-00076
| FIRE-Final Inspection | 3/14/2008 | 3/17/2008 | 3/17/2008 11:46:04 AM | A | PASS |
|
|
Items on correction notice are complete, door closures adjacent to the common corridor to be adjusted prior to structural final for verification, remainder of fire life safety inspection passed.
|
BLD06-00075
| FIRE-Final Inspection | 3/14/2008 | 3/17/2008 | 3/17/2008 11:43:18 AM | A | PASS |
|
|
items on correction notice are complete, door closures adjacent to the common corridor to be adjusted prior to structural final as discussed.
|
FIR07-00235
| INSP-Final Inspection | 3/14/2008 | 3/17/2008 | 3/17/2008 11:41:05 AM | A | PASS |
|
|
Noted corrections verified for completion, fire sprinkler permit finaled.
|