Inspections for the day of: Tuesday, March 17, 2009.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ESC09-00016 General Inspection3/17/20093/17/20093/17/2009 2:58:30 PMPPASS
site ok
ELE09-00413 Electrical Rough-In3/16/20093/17/20093/17/2009 2:57:38 PMPFAIL
lars - please call ahead for access Phone #: ###-#### called corr do not cover posted
210.52(A) needs outlet wall space fam. rm.
314.16 box fill 2 bed rms upstairs, and din. rm. 210.52(B) remove range hood from kit. SABC, 314.20 all outside boxes shall be flush with siding at time of r/i, 334.23 protect cables within 6ft of attic access, 250.148 splice all equip. grds together 2 gang left of kit. sink, 110.3(A) shall provide 16"x20" access for j tub equip per manufacture's instructions at time of r/i, j tub listing ok
ESC09-00072 General Inspection3/17/20093/17/20093/17/2009 1:22:15 PMPPART
ok needs some clean up will stop back
ELE09-00435 Electrical Rough-In3/17/20093/17/20093/17/2009 1:20:46 PMPPASS
Tomas Phone #: ###-#### ok
ELE09-00435 Permanent Service3/17/20093/17/20093/17/2009 1:20:39 PMPPASS
Tomas Phone #: ###-#### p/s u/g new ok
ESC03-01262 DOC - Permit Expired3/17/20093/17/20093/17/2009 10:32:12 AMAPASS
ESC03-01264 DOC - Permit Expired3/17/20093/17/20093/17/2009 10:31:40 AMAPASS
ESC03-01263 DOC - Permit Expired3/17/20093/17/20093/17/2009 10:31:04 AMAPASS
ESC03-00936 DOC - Permit Expired3/17/20093/17/20093/17/2009 10:30:24 AMAPASS
ELE09-00426 Electrical Rough-In3/16/20093/17/20093/17/2009 9:45:32 AMAPART
Shawn ###-#### west and back walls ok only, called needs to secure MC 12" at panel
ELE08-03297 Final3/16/20093/17/20093/17/2009 9:07:54 AMAFAIL
Please call for access code ###-#### Phone #: ###-#### Internet Inspection Request from: Rhonda Yoast corr. called 110.3(A) install all plates, fixture trims, and ironing board, 210.52(C)(1) needs recept within 24" right of range, 406.4 front porch recept loose, 410.2&16 clearence for MB closet fixture
ESC08-00974 General Inspection3/17/20093/17/20093/17/2009 9:04:48 AMAPASS
site ok