Inspections for the day of: Tuesday, March 17, 2009.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00728 INSP-Final Inspection3/16/20093/17/20093/18/2009 4:47:13 PMPPART
Final pending addition of notification at the breakroom area in the detatched shop building, need to locate knox box per fire dept. instructions-see fire code review note #21, also need to provide a list of signals from field testing completed 3/18.
FIR08-00766 INSP-Sprinkler Rough-in/Hydro3/16/20093/17/20093/17/2009 3:48:40 PMPNR
Brian Phone #: ###-####
FIR08-00018 INSP-Sprinkler Rough-in/Hydro3/16/20093/17/20093/17/2009 3:48:07 PMPFAIL
Overhead hydrostatic test for the 1st floor failed due to a 6 psi. pressure loss at the guage. Overhead hydrostatic testing for the 3rd and 4th floors passed.
FIR09-00137 INSP-Sprinkler Rough-in3/16/20093/17/20093/17/2009 3:31:03 PMPPART
See plan annotations for locations of repairs to be made including two upright heads obstructed by adjacent ductwork, deficient existing seismic bracing at the 3" main within the scope of remodel area, dry pendent at the new cooler has not yet been installed. Remainder of overhead modifications okayed.
BLD09-00260 FIRE-Final Inspection3/17/20093/17/20093/17/2009 3:24:50 PMPFAIL
Missing one required fire extinguisher (2A 10BC rated) with a current inspection/certification tag, also need to provide max occupant load sign for the new calculated number. See permit review notes for details.
FIR05-00500 INSP-Final Inspection3/16/20093/17/20093/17/2009 12:58:36 PMAPASS
Fire alarm permit work passed field testing, final approved.
BLD05-01660 FIRE-Final Inspection3/16/20093/17/20093/17/2009 12:57:15 PMAPASS
Fire life safety inspection completed satisfactory, noted repairs finished.
FIR09-00149 INSP-Final Inspection3/16/20093/17/20093/17/2009 12:55:51 PMAPASS
Fire alarm modifications passed inspection, contractor to provide missing lockout at the breaker to the FACP and revise the map to indicate correct sprinkler riser location and added MP at the new mezzanine.