FIR08-00728
| INSP-Final Inspection | 3/16/2009 | 3/17/2009 | 3/18/2009 4:47:13 PM | P | PART |
|
|
Final pending addition of notification at the breakroom area in the detatched shop building, need to locate knox box per fire dept. instructions-see fire code review note #21, also need to provide a list of signals from field testing completed 3/18.
|
FIR08-00766
| INSP-Sprinkler Rough-in/Hydro | 3/16/2009 | 3/17/2009 | 3/17/2009 3:48:40 PM | P | NR |
|
|
Brian Phone #: ###-####
|
FIR08-00018
| INSP-Sprinkler Rough-in/Hydro | 3/16/2009 | 3/17/2009 | 3/17/2009 3:48:07 PM | P | FAIL |
|
|
Overhead hydrostatic test for the 1st floor failed due to a 6 psi. pressure loss at the guage. Overhead hydrostatic testing for the 3rd and 4th floors passed.
|
FIR09-00137
| INSP-Sprinkler Rough-in | 3/16/2009 | 3/17/2009 | 3/17/2009 3:31:03 PM | P | PART |
|
|
See plan annotations for locations of repairs to be made including two upright heads obstructed by adjacent ductwork, deficient existing seismic bracing at the 3" main within the scope of remodel area, dry pendent at the new cooler has not yet been installed. Remainder of overhead modifications okayed.
|
BLD09-00260
| FIRE-Final Inspection | 3/17/2009 | 3/17/2009 | 3/17/2009 3:24:50 PM | P | FAIL |
|
|
Missing one required fire extinguisher (2A 10BC rated) with a current inspection/certification tag, also need to provide max occupant load sign for the new calculated number. See permit review notes for details.
|
FIR05-00500
| INSP-Final Inspection | 3/16/2009 | 3/17/2009 | 3/17/2009 12:58:36 PM | A | PASS |
|
|
Fire alarm permit work passed field testing, final approved.
|
BLD05-01660
| FIRE-Final Inspection | 3/16/2009 | 3/17/2009 | 3/17/2009 12:57:15 PM | A | PASS |
|
|
Fire life safety inspection completed satisfactory, noted repairs finished.
|
FIR09-00149
| INSP-Final Inspection | 3/16/2009 | 3/17/2009 | 3/17/2009 12:55:51 PM | A | PASS |
|
|
Fire alarm modifications passed inspection, contractor to provide missing lockout at the breaker to the FACP and revise the map to indicate correct sprinkler riser location and added MP at the new mezzanine.
|