FIR09-00708
| INSP-Sprinkler Rough-in | 3/17/2010 | 3/17/2010 | 3/18/2010 6:23:08 PM | P | PART |
|
|
See annotations initialed with today's date on sheet FP-4 including the library, private dining, activity, and TV lounge rooms okayed for ceiling cover. NOTE: Soffits at the adjacent hallway and library/dining rooms are not yet approved for cover due to batt insulation blocking attic sprinkler coverage in these combustible pockets- Discussed solutions with contractor on site.
|
FIR08-00418
| FIR-Aging Inspection | 3/17/2010 | 3/17/2010 | 3/18/2010 6:14:33 PM | P | FAIL |
|
|
Missing one pendent sprinkler head at the first floor stairway landing south side, remainder of permit work is acceptable.
|
BLD10-00122
| FIRE-Final Inspection | 3/16/2010 | 3/17/2010 | 3/17/2010 2:22:00 PM | A | PASS |
|
|
Fire life safety is acceptable pending approved hardware is provided at two pocket doors prior to structural inspection for verification at that time, one fire extinguisher at the south side tenant posted while on site, inspection passed.
|
FIR07-00618
| INSP-Final Inspection | 3/12/2010 | 3/17/2010 | 3/17/2010 2:14:59 PM | A | PASS |
|
|
Fire sprinkler permit finaled. Discussed adjacent tenant remodel work including open pemit # FIR08-00418.
|
FIR09-00707
| INSP-Sprinkler Rough-in | 3/16/2010 | 3/17/2010 | 3/17/2010 2:10:24 PM | A | PART |
|
|
See stamped plan set sheet FP-4 for clouded area initialed and marked with today's date for locations of overhead work at sheetrock ceilings okayed for cover. Missing coverage at one adjacent vestibule to be verified prior to cover and not included in this inspection.
|
FIR02-00442
| INSP-Conference | 3/16/2010 | 3/17/2010 | 3/17/2010 1:23:59 PM | P | DONE |
|
|
Permit expired- see scope of work completed for subsequent permits at this building.
|
FIR05-00600
| INSP-Conference | 3/16/2010 | 3/17/2010 | 3/17/2010 1:21:06 PM | P | DONE |
|
|
Permit expired per conversation with contractor.
|
FIR06-00072
| INSP-Conference | 3/16/2010 | 3/17/2010 | 3/17/2010 1:19:24 PM | A | DONE |
|
|
Permit expired
|
FIR08-00860
| INSP-Final Inspection | 3/17/2010 | 3/17/2010 | 3/17/2010 1:15:23 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR08-00860
| INSP-Final Inspection | 3/16/2010 | 3/17/2010 | 3/17/2010 1:14:54 PM | A | PASS |
|
|
On site meeting with contractor to review scope of work and annotated plans.
|
FIR08-00809
| INSP-Conference | 3/16/2010 | 3/17/2010 | 3/17/2010 1:13:55 PM | A | DONE |
|
|
Work on this project has been suspended, project abandoned- okay to expire permit per conversation with contractor.
|