Inspections for the day of: Wednesday, March 17, 2010.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00708 INSP-Sprinkler Rough-in3/17/20103/17/20103/18/2010 6:23:08 PMPPART
See annotations initialed with today's date on sheet FP-4 including the library, private dining, activity, and TV lounge rooms okayed for ceiling cover. NOTE: Soffits at the adjacent hallway and library/dining rooms are not yet approved for cover due to batt insulation blocking attic sprinkler coverage in these combustible pockets- Discussed solutions with contractor on site.
FIR08-00418 FIR-Aging Inspection3/17/20103/17/20103/18/2010 6:14:33 PMPFAIL
Missing one pendent sprinkler head at the first floor stairway landing south side, remainder of permit work is acceptable.
BLD10-00122 FIRE-Final Inspection3/16/20103/17/20103/17/2010 2:22:00 PMAPASS
Fire life safety is acceptable pending approved hardware is provided at two pocket doors prior to structural inspection for verification at that time, one fire extinguisher at the south side tenant posted while on site, inspection passed.
FIR07-00618 INSP-Final Inspection3/12/20103/17/20103/17/2010 2:14:59 PMAPASS
Fire sprinkler permit finaled. Discussed adjacent tenant remodel work including open pemit # FIR08-00418.
FIR09-00707 INSP-Sprinkler Rough-in3/16/20103/17/20103/17/2010 2:10:24 PMAPART
See stamped plan set sheet FP-4 for clouded area initialed and marked with today's date for locations of overhead work at sheetrock ceilings okayed for cover. Missing coverage at one adjacent vestibule to be verified prior to cover and not included in this inspection.
FIR02-00442 INSP-Conference3/16/20103/17/20103/17/2010 1:23:59 PMPDONE
Permit expired- see scope of work completed for subsequent permits at this building.
FIR05-00600 INSP-Conference3/16/20103/17/20103/17/2010 1:21:06 PMPDONE
Permit expired per conversation with contractor.
FIR06-00072 INSP-Conference3/16/20103/17/20103/17/2010 1:19:24 PMADONE
Permit expired
FIR08-00860 INSP-Final Inspection3/17/20103/17/20103/17/2010 1:15:23 PMPPASS
Fire sprinkler permit finaled.
FIR08-00860 INSP-Final Inspection3/16/20103/17/20103/17/2010 1:14:54 PMAPASS
On site meeting with contractor to review scope of work and annotated plans.
FIR08-00809 INSP-Conference3/16/20103/17/20103/17/2010 1:13:55 PMADONE
Work on this project has been suspended, project abandoned- okay to expire permit per conversation with contractor.