Inspections for the day of: Thursday, March 17, 2011.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-02470 ELE-Aging Inspection3/17/20113/17/20113/21/2011 7:32:13 AM DONE
still under construction
ELE11-00493 Electrical Rough-In3/17/20113/17/20113/17/2011 2:59:15 PMPPASS
Call Mike - Russell Corporation (###-####) 20 minutes prior to your arrival and he can let you in. ri ok

MECi Contact - Clay Jackson (###-####) Phone #: ###-#### >> Inspection requested via web by Danny Smith
ELE11-00096 Electrical Rough-In3/17/20113/17/20113/17/2011 2:48:16 PMPPASS
basement inspection. Please call John. Phone #: ###-#### >> Inspection requested via web by John Campbell ok cover basement ceiling anop
ELE11-00267 Permanent Service3/17/20113/17/20113/17/2011 1:46:24 PMPPASS
Service change. Jeff will be on the job. Phone #: ###-#### >> Inspection requested via web by Brandon Blackham p/s u/g rec ok
ELE11-00488 Electrical Rough-In3/16/20113/17/20113/17/2011 1:30:12 PMPPASS
Phone #: ###-#### >> Inspection requested via web by JENNY EMEL soffits and walls ok cover
ELE10-00353 Final3/17/20113/17/20113/17/2011 12:41:02 PMPFAIL
Kevin Phone #: ###-#### called, shall provide abrasion protection for gec, shall add 2nd ground rod and tighten clamp, yhen re-call for inspection,NOTE- owner said will be changing out sub-panel this summer
ELE10-02830 ELE-Aging Inspection3/17/20113/17/20113/17/2011 11:37:37 AM DONE
still under construction
ELE11-00014 Final3/16/20113/17/20113/17/2011 10:09:09 AMAPASS
Phone #: ###-#### >> Inspection requested via web by PAT MILLER ok final
ELE11-00311 Rough-In Permanent Service3/16/20113/17/20113/17/2011 9:51:58 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Zane Robertson corrections made, ri ok, p/s u/g n ok
ELE11-00115 Final3/16/20113/17/20113/17/2011 9:07:27 AMAPASS
Cal Phone #: ###-#### >> Inspection requested via web by cal crosby ok final
ELE11-00487 Electrical Rough-In3/16/20113/17/20113/17/2011 8:28:42 AMAFAIL
justin - please call for access Phone #: ###-#### met contractor, left correction notice, NEC 300.4(D) edge of cable shall be 1 1/4" from edge of framing member, 330.30(A) shall strap mc within 12" of ternination, BCC shall not wire in valley of 2x4, shall close breaker opening and boxes, no lv wiring on grid in ceiling, no violations shall be retained