ELE10-02470
| ELE-Aging Inspection | 3/17/2011 | 3/17/2011 | 3/21/2011 7:32:13 AM | | DONE |
|
|
still under construction
|
ELE11-00493
| Electrical Rough-In | 3/17/2011 | 3/17/2011 | 3/17/2011 2:59:15 PM | P | PASS |
|
|
Call Mike - Russell Corporation (###-####) 20 minutes prior to your arrival and he can let you in. ri ok
MECi Contact - Clay Jackson (###-####) Phone #: ###-#### >> Inspection requested via web by Danny Smith
|
ELE11-00096
| Electrical Rough-In | 3/17/2011 | 3/17/2011 | 3/17/2011 2:48:16 PM | P | PASS |
|
|
basement inspection. Please call John. Phone #: ###-#### >> Inspection requested via web by John Campbell ok cover basement ceiling anop
|
ELE11-00267
| Permanent Service | 3/17/2011 | 3/17/2011 | 3/17/2011 1:46:24 PM | P | PASS |
|
|
Service change. Jeff will be on the job. Phone #: ###-#### >> Inspection requested via web by Brandon Blackham p/s u/g rec ok
|
ELE11-00488
| Electrical Rough-In | 3/16/2011 | 3/17/2011 | 3/17/2011 1:30:12 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by JENNY EMEL soffits and walls ok cover
|
ELE10-00353
| Final | 3/17/2011 | 3/17/2011 | 3/17/2011 12:41:02 PM | P | FAIL |
|
|
Kevin Phone #: ###-#### called, shall provide abrasion protection for gec, shall add 2nd ground rod and tighten clamp, yhen re-call for inspection,NOTE- owner said will be changing out sub-panel this summer
|
ELE10-02830
| ELE-Aging Inspection | 3/17/2011 | 3/17/2011 | 3/17/2011 11:37:37 AM | | DONE |
|
|
still under construction
|
ELE11-00014
| Final | 3/16/2011 | 3/17/2011 | 3/17/2011 10:09:09 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by PAT MILLER ok final
|
ELE11-00311
| Rough-In Permanent Service | 3/16/2011 | 3/17/2011 | 3/17/2011 9:51:58 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Zane Robertson corrections made, ri ok, p/s u/g n ok
|
ELE11-00115
| Final | 3/16/2011 | 3/17/2011 | 3/17/2011 9:07:27 AM | A | PASS |
|
|
Cal Phone #: ###-#### >> Inspection requested via web by cal crosby ok final
|
ELE11-00487
| Electrical Rough-In | 3/16/2011 | 3/17/2011 | 3/17/2011 8:28:42 AM | A | FAIL |
|
|
justin - please call for access Phone #: ###-#### met contractor, left correction notice, NEC 300.4(D) edge of cable shall be 1 1/4" from edge of framing member, 330.30(A) shall strap mc within 12" of ternination, BCC shall not wire in valley of 2x4, shall close breaker opening and boxes, no lv wiring on grid in ceiling, no violations shall be retained
|