Inspections for the day of: Thursday, March 17, 2011.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00213 FIR-Aging Inspection3/17/20113/17/20113/18/2011 5:01:26 PM PEND
FIR10-00169 FIR-Aging Inspection3/17/20113/17/20113/18/2011 4:57:05 PM PEND
BLD11-00430 FIRE-Final Inspection3/16/20113/17/20113/18/2011 4:50:53 PMAPART
Need to repair three existing EM lights.
FIR11-00115 INSP-Sprinkler Rough-in3/17/20113/17/20113/17/2011 4:59:05 PMPPART
Overhead fire sprinkler work okayed for cover at the remodel area.
FIR10-00415 INSP-Final Inspection3/15/20113/17/20113/17/2011 2:17:06 PMAFAIL
Speakers are not operational.
FIR10-00355 INSP-Final Inspection3/15/20113/17/20113/17/2011 2:11:16 PMAPART
Verified dry system pressure switch and outside bell operations. Need to complete forward flow test per last inspection notes dated 2/14 and per plan review revision notes item #1 dated 8/11/10. Missing automatic air maintenance device per NFPA 13 7.2.6.5.1 or meet sec. 7.2.6.5.2.
BLD10-00842 FIRE-Final Inspection3/16/20113/17/20113/17/2011 1:59:07 PMANR
Previous correction notice items regarding building fire life safety verified for completion. Final pending project related FIR permits.
FIR10-00654 INSP-Final Inspection3/16/20113/17/20113/17/2011 1:55:39 PMAPASS
Scope of fire alarm permit work finaled.
FIR10-00648 INSP-Final Inspection3/16/20113/17/20113/17/2011 1:54:39 PMAPASS
Reinspection passed, fire alarm permit finaled.